11.22 Parameters Changed by PM Motor Code Selection
624
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-09
PM Back-EMF Vpeak
(mV/(rad/s))
mVs/rad
320.4
327.1
364.4
344.4
357.5
430.8
391.5
384.4
E5-24
PM Back-EMF L-L
Vrms (mV/rpm)
mV/min
-1
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Output
Voltage
V
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Minimum Output
Frequency
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm
2
0.0017
0.0023
0.0083
0.0136
0.0171
0.027
0.046
0.055
L3-24
Motor Accel Time @
Rated Torque
s
0.062
0.044
0.080
0.090
0.067
0.072
0.088
0.073
n5-02
Motor Inertia
Acceleration Time
s
0.062
0.044
0.080
0.090
0.067
0.072
0.088
0.073
n8-49
Heavy Load Id Current
%
-8.8
-9.9
-9.3
-10.0
-17.7
-12.3
-15.3
-13.9
*1
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
Table 11.17 SSR1 Series Motor Code Setting for Specification of 200 V at 1150 min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-01
PM Motor Code Selection
-
140E
140F
1410
1412
1413
1414
Voltage Class
V
200
200
200
200
200
200
Capacity
kW
15
18
22
30
37
45
Motor Rotation Speed
min
-1
1150
1150
1150
1150
1150
1150
E5-02
PM Motor Rated Power
kW
15
18.50
22.00
30.00
37.00
45.00
E5-03
PM Motor Rated Current
(FLA)
A
55.6
63.5
74.4
104.2
129.6
154.2
E5-04
PM Motor Pole Count
-
6
6
6
6
6
6
E5-05
PM Motor Resistance (ohms/
phase)
Ω
0.084
0.066
0.048
0.035
0.023
0.016
E5-06
PM d-axis Inductance (mH/
phase)
mH
3.83
3.33
2.38
2.04
1.53
1.16
E5-07
PM q-axis Inductance (mH/
phase)
mH
4.65
4.50
3.15
2.86
2.27
1.54
E5-09
PM Back-EMF Vpeak (mV/
(rad/s))
mVs/rad
372.1
421.3
410.9
436.1
428.8
433.3
E5-24
PM Back-EMF L-L Vrms
(mV/rpm)
mV/min
-1
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Output Voltage
V
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Minimum Output Frequency
Hz
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm
2
0.064
0.116
0.140
0.259
0.312
0.418
L3-24
Motor Accel Time @ Rated
Torque
s
0.062
0.091
0.092
0.125
0.122
0.135
n5-02
Motor Inertia Acceleration
Time
s
0.062
0.091
0.092
0.125
0.122
0.135
n8-49
Heavy Load Id Current
%
-14.4
-17.9
-15.9
-17.9
-20.1
-13.7
*1
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...