Configuration Parameter
Description
b5-90 [EZ Sleep Unit]
Sets the unit of measure for
b5-92 [EZ Sleep Level]
. When
b5-90 = 0 [0.1Hz units]
, the setting range of
b5-91
[EZ Minimum Speed]
is 0.0 to 590.0 Hz. When
b5-90 = 1 [rev/min]
, the setting range is 0 to 35400 min
-1
(r/
min).
Note:
When you change
b5-90
, the value of
b5-92
is not automatically updated.
b5-91 [EZ Minimum Speed]
This parameter sets the lower limit for PID output. The drive uses the largest value of
b5-91
,
b5-34 [PID Output
Lower Limit]
, and
d2-02 [Frequency Reference Lower Limit]
to internally set the lower limit of PID output. The
b5-89
setting does not have an effect.
b5-92 [EZ Sleep Level]
When the output frequency or motor speed is less than the value of
b5-92
for longer than the value of
b5-93 [EZ
Sleep Time]
, the drive does to sleep.
b5-95 = 0 [EZ Wake-up Mode = Absolute]
When the PID feedback is less than the value of
b5-94 [EZ Wake-up Level]
for longer than the time set in
b5-96
[EZ Sleep Wake-up Time]
, the drive restarts operation from sleep.
b5-95 = 1 [EZ Wake-up Mode = Setpiont Delta]
When the PID feedback is less than the value set as the PID setpoint value minus
b5-94
for the time set in
b5-96
,
the drive restarts operation from sleep.
Figure 12.38 EZ Sleep/Wake-up Operation: PID Output is Normal and b5-92 = 0.0 Hz
*1
The values of
b5-94
and
b5-95
set operation.
*2
In the example,
b5-92
is at the default setting of 0.0 Hz.
b5-91
is the EZ sleep level.
■
b5-01: PID Mode Setting
No.
(Hex.)
Name
Description
Default
(Range)
b5-01
(01A5)
PID Mode Setting
Sets the type of PID control.
0
(0 - 8)
0 : PID control disabled
1 : Standard
Enables PID control. The drive performs D control on the difference between the feedback value and the PID setpoint
output via
U5-02 [PID Input]
.
2 : Standard (D on feedback)
Enables PID control. The drive performs D control on the feedback output via
U5-06 [PID Fdbk-Diff PID Fdbk]
.
3 : Fref + PID Trim
Enables PID control. The drive adds the frequency reference to the PID output. The drive performs D control on the
difference between the feedback value and the PID setpoint output via
U5-02 [PID Input]
.
4 : Fref + PID Trim (D on feedback)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...