890
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
You must use the Enter command to enable changes to parameters. Make all parameter changes then input the Enter
command.
1 : ENTER Command Not Required
It is not necessary to input the Enter command to change parameters.
■
H5-12: Run Command Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-12
(043D)
Run Command Method
Selection
Sets the input method for the Run command when
b1-02 = 2 [Run Command Selection 1 =
Memobus/Modbus Communications]
or
b1-16 = 2 [Run Command Selection 2 = Memobus/Modbus
Communications]
.
0
(0, 1)
0 : FWD/Stop, REV/Stop
The drive uses bit 0 in command data 0001H of the MEMOBUS register in the motor forward Run command (bit 0 =
1) and the stop command (bit 0 = 0). The drive uses bit 1 in the motor reverse Run command (bit 1 = 1) and the stop
command (bit 1 = 0).
1 : Run/Stop, FWD/REV
The drive uses bit 0 in command data 0001H of the MEMOBUS register in the motor Run command (bit 0 = 1) and
the stop command (bit 0 = 0). The drive uses bit 1 in the direction of motor rotation command (Forward run (bit1 = 0)
or Reverse run (bit 1 = 1)).
■
H5-17: ENTER command response @CPU BUSY
No.
(Hex.)
Name
Description
Default
(Range)
H5-17
(11A1)
Expert
ENTER command response
@CPU BUSY
Sets operation when the EEPROM write command is sent without EEPROM write available. Usually
it is not necessary to change this setting.
0
(0, 1)
0 : Ignore Command(No ROM/RAM Write)
1 : Write to RAM Only
■
H5-18: Motor Speed Filter over Comms
No.
(Hex.)
Name
Description
Default
(Range)
H5-18
(11A2)
Motor Speed Filter over
Comms
Sets the filter time constant used when monitoring motor speed during MEMOBUS/Modbus
communications or with a communication option.
0 ms
(0 - 100 ms)
Sets the filter time constant when you monitor the output frequency or motor speed during MEMOBUS/Modbus
communications or use of the communication option.
These are the MEMOBUS registers:
•
003EH (Output Frequency)
•
003FH (Output Frequency)
•
0044H (
U1-05
: Motor Speed)
•
00ACH (
U1-05
: Motor Speed)
•
00ADH (
U1-05
: Motor Speed)
■
H5-20: Communication Parameters Reload
No.
(Hex.)
Name
Description
Default
(Range)
H5-20
(0B57)
Communication Parameters
Reload
Sets the function to immediately enable updated MEMOBUS/Modbus communications parameters.
0
(0, 1)
0 : Reload at Next Power Cycle
1 : Reload Now
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...