3.4 Main Circuit Terminal Block Wiring Procedure
88
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Table 3.5 Recommended Wiring Tools
Screw Size
Screw Shape
Adapter
Bit
Torque Driver Model
(Tightening Torque)
Torque Wrench
Model
Manufacturer
M4
Slotted (-)
Bit
SF-BIT-SL 1,0X4,0-70
PHOENIX CONTACT
TSD-M 3NM
(1.2 - 3 N∙m
(10.6 - 26.6 in∙lb))
-
M5
Slotted (-)
Bit
F-BIT-SL 1,2X6,5-70
PHOENIX CONTACT
Wire Gauge ≤
25 mm
2
(AWG 10):
TSD-M 3NM
(1.2 - 3 N∙m
(10.6 - 26.6 in∙lb))
Wire Gauge ≤
25 mm
2
(AWG 10): -
Wire Gauge ≥
30 mm
2
(AWG 8): -
Wire Gauge ≥
30 mm
2
(AWG 8):
4.1 - 4.5 N∙m
(36.3 - 39.8 in∙lb)
M6
Hex socket cap
(WAF: 5 mm)
Bit
SF-BIT-HEX 5-50
PHOENIX CONTACT
-
5 - 9 N∙m
(44.3 - 79.7 in∙lb)
Slotted (-)
Bit
SF-BIT-SL 1,2X6,5-70
PHOENIX CONTACT
-
3 - 3.5 N∙m
(26.6 - 31.0 in∙lb)
M8
Hex socket cap
(WAF: 6 mm)
Bit
SF-BIT-HEX 6-50
PHOENIX CONTACT
-
8 - 12 N∙m
(70.8 - 106.2 in∙lb)
M10
Hex socket cap
(WAF: 8 mm)
Bit
SF-BIT-HEX 8-50
PHOENIX CONTACT
-
12 - 14 N∙m
(106.2 - 123.9 in∙lb)
*1
When wiring drive models 2056 and 4089 and smaller, select the correct tools for the wire gauge.
*2
Use 6.35 mm (0.25 in) bit socket holder.
*3
Use a torque wrench that can apply this torque measurement range.
■
Main Circuit Terminal Block Wiring Procedure
Remove the keypad and front cover before wiring the main circuit terminal block.
1.
Pull the wiring cover away from the drive to remove it.
A - Wiring cover
Figure 3.24 Remove the Wiring Cover
2.
Put the end of a prepared wire into the terminal block.
Figure 3.25 Install the Electrical Wire
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...