SIEPC71061737B GA800 Drive Technical Reference
The overload tolerance is 110% of the rated output current for 60 seconds.
There are two types of load ratings for this product depending on the load characteristics of the application: Heavy
Duty Rating (HD) and Normal Duty Rating (ND).
The drive rated output current, overload tolerance, and acceleration stall prevention level change when the duty rating
changes. Set the drive to agree with the duty rating of the selected drive capacity. In HD, the tolerance is 150%
overload for 60 seconds. In ND, the tolerance is 110% overload for 60 seconds. The rated output current for ND
drives is higher than the rated output current for HD drives. Refer to
“
Model Specifications (200 V Class)
”
and
“
Model Specifications (400 V Class)
”
for more information about rated output current.
Table 12.34 Differences between Heavy Duty Rating and Normal Duty Rating
Item
Heavy Duty Rating (HD)
Normal Duty Rating (ND)
C6-01 Setting
0
1
Load Characteristics
Application
A high overload tolerance is necessary during start up, acceleration,
deceleration, and equivalent conditions.
•
Extruder
•
Conveyor
•
Constant torque or high overload capacity are necessary.
Overload tolerance is not necessary.
•
Fan
•
Pump
•
Blower
Overload Tolerance
150% - 60 seconds
110% - 60 seconds
Stall Prevent Level during Accel
150%
110%
Stall Prevent Level during Run
150%
110%
Carrier Frequency
2 kHz
2 kHz Swing-PWM
Note:
•
Set the stall prevention level during acceleration with
L3-02
and the stall prevention level during run with
L3-06
.
•
Changing
C6-01
also changes the maximum capacity of applicable drive motors. The drive automatically changes the setting values
E2-xx
and
E4-xx
to applicable values. The drive also automatically changes these parameters that depend on motor output:
–
b8-04 [Energy Saving Coefficient Value]
–
C5-17 [Motor Inertia]
–
C5-37 [Motor 2 Inertia]
–
L2-03 [Minimum Baseblock Time]
–
L3-24 [Motor Accel Time @ Rated Torque]
–
n5-02 [Motor Inertia Acceleration Time]
■
C6-02: Carrier Frequency Selection
No.
(Hex.)
Name
Description
Default
(Range)
C6-02
(0224)
Carrier Frequency Selection
Sets the carrier frequency for the transistors in the drive.
Determined by A1-02, C6-
01, and o2-04
(Determined by A1-02)
Changes to the switching frequency will decrease audible noise and decrease leakage current.
Note:
Increasing the carrier frequency to more than the default setting will automatically decrease the drive current rating.
1 : 2.0 kHz
2 : 5.0 kHz (4.0 kHz AOLV/PM)
3 : 8.0 kHz (6.0 kHz AOLV/PM)
4 : 10.0 kHz (8.0 kHz AOLV/PM)
5 : 12.5 kHz (10.0 kHz AOLV/PM)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...