338
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Code
Name
Causes
Possible Solutions
The option card is damaged.
If the alarm continues and the wiring is correct, replace the option
card.
Note:
•
The drive detects this error if the Run command or frequency reference is assigned to the option card.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will activate.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
F6-01 [Communication Error Selection]
.
Code
Name
Causes
Possible Solutions
CALL
Serial Comm Transmission Error
The communications cable wiring is incorrect.
Correct wiring errors.
There is a short circuit in the communications cable
or the communications cable is not connected.
•
Repair the short-circuited or disconnected portion of the cable.
•
Replace the defective communications cable.
A programming error occurred on the controller side.
Examine communications at start-up and correct programming
errors.
There is damage to the communications circuitry.
•
Do a self-diagnostics check.
•
If the problem continues, replace the control board or the drive.
Contact Yaskawa or your nearest sales representative to replace
the control board.
The termination resistor setting for MEMOBUS/
Modbus communications is incorrect.
On the last drive in a MEMOBUS/Modbus network, set DIP switch
S2 to the ON position to enable the termination resistor.
Note:
•
The drive detects this error if it does not correctly receive control data from the controller when energizing the drive.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
CE
Modbus Communication Error
The communications cable wiring is incorrect.
Correct wiring errors.
There is a short circuit in the communications cable
or the communications cable is not connected.
•
Repair short circuits and connect cables.
•
Replace the defective communications cable.
Electrical interference caused a communication data
error.
•
Examine the control circuit lines, main circuit lines, and ground
wiring, and decrease the effects of electrical interference.
•
Make sure that a magnetic contactor is not the source of the
electrical interference, then use a Surge Protective Device if
necessary.
•
Use only the recommended cables or other shielded line. Ground
the shield on the controller side or the drive input power side.
•
Separate the communication wiring from drive power lines, and
install a noise filter to the input side of the power supply for
communication.
•
Decrease the effects of electrical interference from the controller.
The communication protocol is not compatible.
•
Examine the values set in
H5-xx
.
•
Examine the settings on the controller side and correct the
difference in communication conditions.
The value set in
H5-09 [CE Detection Time]
is too
small for the communications cycle.
•
Change the controller software settings.
•
Increase the value set in
H5-09
.
The controller software or hardware is causing a
communication problem.
Examine the controller and remove the cause of the problem.
Note:
•
The drive detects this error if it does not correctly receive control data for the
CE
detection time set to
H5-09
.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
H5-04 [Communication Error Stop Method]
.
Code
Name
Causes
Possible Solutions
CP1
Comparator 1 Limit Error
The monitor value set in
H2-20 [Comparator 1
Monitor Selection]
was in the range of
H2-21
[Comparator 1 Lower Limit]
and
H2-22
[Comparator 1 Upper Limit]
.
Examine the monitor value and remove the cause of the error.
Note:
•
The drive detects this error when the terminal is assigned to
H2-01 to H2-03 = 66 [MFDO Function Select = Comparator1]
.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
•
H2-33 [Comparator1 Protection Selection]
enables and disables
CP1
detection.
Code
Name
Causes
Possible Solutions
CP2
Comparator 2 Limit Error
The monitor value set in
H2-26 [Comparator 2
Monitor Selection]
was outside the range of
H2-27
[Comparator 2 Lower Limit]
and
H2-28
[Comparator 2 Upper Limit]
.
Examine the monitor value and remove the cause of the error.
Note:
•
The drive detects this error when the terminal is assigned to
H2-01 to H2-03 = 67 [MFDO Function Select = Comparator2]
.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
•
H2-35 [Comparator2 Protection Selection]
enables and disables
CP2
detection.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...