When the
Up/Down 2 Command [H1-xx = 75, 76]
is active, the drive uses the accel/decel times set in
d4-04 [Up/
Down 2 Ramp Selection]
to increase or decrease the bias value.
Figure 12.66 Up/Down 2 Bias when d4-03 = 0.00 Hz
•
Setting d4-03 ≠ 0.00 Hz
When the
Up/Down 2 Command [H1-xx = 75, 76]
is active, the drive increases or decreases the bias in steps for the
value set in
d4-03
. The drive uses the acceleration and deceleration times set in
d4-04
.
Figure 12.67 Up/Down 2 Bias when d4-03
≠
0.00 Hz
■
d4-04: Up/Down 2 Ramp Selection
No.
(Hex.)
Name
Description
Default
(Range)
d4-04
(02AB)
RUN
Up/Down 2 Ramp Selection
Sets the acceleration and deceleration times for the Up/Down 2 function to apply the bias to the
frequency reference.
0
(0, 1)
0 : Use Selected Accel/Decel Time
Use the active acceleration and deceleration times to increase or decrease the bias.
1 : Use Accel/Decel Time 4
Use
C1-07 [Acceleration Time 4]
and
C1-08 [Deceleration Time 4]
to increase or decrease the bias.
■
d4-05: Up/Down 2 Bias Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
d4-05
(02AC)
RUN
Up/Down 2 Bias Mode
Selection
Sets the function that saves the bias value to the drive when you open or close the two
Up/Down 2
Commands [H1-xx = 75, 76]
. Set
d4-03 [Up/Down 2 Bias Step Frequency] = 0.00
before you set this
parameter.
0
(0, 1)
0 : Hold when Neither Up/Down Closed
When the two MFDI terminals set for
Up/Down 2 Command [H1-xx = 75, 76]
activate or deactivate, the drive will
hold the bias value.
1 : Reset when Neither / Both Closed
When the two MFDI terminals set for
Up/Down 2 Command [H1-xx = 75, 76]
activate or deactivate, the drive will
reset the bias value to 0. The drive will use the acceleration and deceleration times set in
d4-04 [Up/Down 2 Ramp
Selection]
to accelerate and decelerate the motor to the selected output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...