YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
795
output voltage range of -10 V to +10 V. Install the AO-A3 card to a drive to output analog signals that monitor the
output status of the drive (output frequency and output current).
Refer to the AO-A3 card manual for more information about how to install, wire, and set the AO-A3 card.
Use the
U monitor
number to set the monitor data to be output from terminals V1 and V2 on the AO-A3 card. Enter
the last three digits of
Ux-xx
as the setting value.
•
Use Gain and Bias to Adjust the Output Signal Level of Terminal V1
You must stop the drive to adjust the output signal. Use this procedure to calibrate the drive:
1. View the
F4-02 [Terminal V1 Gain]
value on the keypad.
Terminal V1 will output a voltage = 100% of the monitor set in
F4-01 [Terminal V1 Function Selection]
.
2. View the monitor connected to terminal V1 and adjust
F4-02
.
3. View the
F4-05 [Terminal V1 Bias]
value on the keypad.
Terminal V1 will output an analog signal = 100% of the parameter set in
F4-01
.
4. View the monitor connected to terminal V1 and adjust
F4-05
.
•
Use Gain and Bias to Adjust the Output Signal Level of Terminal V2
You must stop the drive to adjust the output signal. Use this procedure to calibrate the drive:
1. View the
F4-04 [Terminal V2 Gain]
value on the keypad.
Terminal V2 will output a voltage = 100% of the monitor set in
F4-03 [Terminal V2 Function Selection]
.
2. View the monitor connected to terminal V2 and adjust
F4-04
.
3. View the
F4-06 [Terminal V2 Bias]
value on the keypad.
The analog signal equal to 0% of the parameter being set in
F4-03
will be output from terminal V2.
4. View the monitor connected to terminal V2 and adjust
F4-06
.
■
F4-01: Terminal V1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F4-01
(0391)
Terminal V1 Function
Selection
Sets the monitor signal output from terminal V1.
102
(000 - 999)
Set the
x-xx
part of the
Ux-xx [Monitors]
to set monitor data to output from the option card. For example, set
F4-01 =
102
to monitor
U1-02 [Output Frequency]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can use MEMOBUS/Modbus communications or the
communication option to set the terminal V1 output level from the PLC.
■
F4-02: Terminal V1 Gain
No.
(Hex.)
Name
Description
Default
(Range)
F4-02
(0392)
RUN
Terminal V1 Gain
Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal output level
from the terminal V1 at 10 V or 20 mA as 100% when an output for monitoring items is 100%.
100.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V1 is ±10 V. Use
F4-07 [Terminal V1 Signal Level]
to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage of
terminal V1 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V1 outputs a
maximum voltage of 10 V.
•
F4-01 [Terminal V1 Function Selection] = 102 (U1-02: Output Frequency)
•
F4-02 = 50.0%
•
F4-05 [Terminal V1 Bias] = 0.0%
•
F4-07 = 0 (0 V to 10 V)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...