YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
695
4 : Alarm + Digital Out, @PID Enable
The drive detects
FbL
and
FbH
. The MFDO terminal set for
PID Feedback Low
or
PID Feedback High
activates. The
output terminal set for
Alarm [H2-01 to H2-03 = 10]
activates and the drive continues operation.
When the MFDI terminal set to
PID Disable [H1-xx = 19]
activates, the drive disables fault detection.
5 : Fault + Digital Out, @PID Enable
The drive detects
FbL
and
FbH
. Fault relay output terminal MA-MC activates, MB-MC turns OFF, and the drive
coasts to stop.
When the MFDI terminal set to
PID Disable [H1-xx = 19]
activates, the drive disables fault detection.
■
b5-13: PID Feedback Loss Detection Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b5-13
(01B1)
PID Feedback Loss
Detection Lvl
Sets the level that triggers
PID Feedback Loss [FbL]
detection as a percentage of the Maximum
Output Frequency.
0%
(0 - 100%)
The drive detects
PID Feedback Loss [FbL]
when the feedback signal decreases to less than the level set in
b5-13
for
longer than the time set in
b5-14 [PID Feedback Loss Detection Time]
.
■
b5-14: PID Feedback Loss Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-14
(01B2)
PID Feedback Loss
Detection Time
Sets the length of time that PID Feedback must be less than
b5-13 [PID Feedback Loss Detection
Lvl]
to detect
PID Feedback Loss [FbL]
.
1.0 s
(0.0 - 25.5 s)
■
b5-15: PID Sleep Function Start Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-15
(01B3)
PID Sleep Function Start
Level
Sets the output level that triggers the PID Sleep function.
Determined by A1-02
(0.0 - 590.0)
The drive goes into Sleep mode when the PID output or frequency reference is less than
b5-15
for longer than the
time set to
b5-16 [PID Sleep Delay Time]
. The drive continues operation when the PID output or frequency reference
is more than
b5-15
for longer than the time set to
b5-16
.
■
b5-16: PID Sleep Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-16
(01B4)
PID Sleep Delay Time
Sets a delay time to start or stop the PID Sleep function.
0.0 s
(0.0 - 25.5 s)
■
b5-17: PID Accel/Decel Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-17
(01B5)
RUN
PID Accel/Decel Time
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the drive. This
is a soft-starter for the PID setpoint.
0.0 s
(0.0 - 6000.0 s)
The drive usually uses the acceleration and deceleration times set in
C1-xx [Accel and Decel Times]
, but when PID
control is enabled, the drive applies
C1-xx
after PID output. If you frequently change the PID setpoint, the drive
responsiveness decreases. When resonance with PID control causes hunting, overshoot, or undershoot, set
b5-17
for
longer acceleration and deceleration times.
Decrease
C1-xx
until hunting stops, then use
b5-17
to check the acceleration and deceleration. To enable and disable
the setting in
b5-17
through an MFDI terminal, set
PID Soft Starter Disable [H1-xx = 34]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...