6.3 MEMOBUS/Modbus Communications
284
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Table 6.11 MEMOBUS/Modbus Communications Command Data
Register No.
(Hex.)
Description
0000
Reserved
0001
Run command, multi-function input command
bit 0
When
H5-12 = 0
, Forward run/stop
1: Forward run, 0: Stop
When
H5-12 = 1
, run/stop
1: Run, 0: Stop
bit 1
When
H5-12 = 0
, Reverse run/stop
1: Reverse run, 0: Stop
When
H5-12 = 1
, Forward/Reverse run
1: Reverse, 0: Forward run
bit 2
External fault
1: EF0 [Option Card External Fault]
bit 3
Fault Reset
1: Reset command
bit 4
Multi-function input 1
When
H1-01 = 40 [Forward Run Command (2-Wire Seq)]
, the multi-function input command is
“
ComRef.
”
Note:
When you switch the bit ON as ComRef, the frequency reference source changes to MEMOBUS/Modbus communications.
When you connect a communication option to the drive, the frequency reference source gives priority to the communications
option.
bit 5
Multi-function input 2
When the multi-function input command is
H1-02 = 41 [Reverse Run Command (2-Wire Seq)]
, bit 5 is
“
ComCtrl.
”
Note:
When you switch the bit ON as ComCtrl, the Run Command source changes to MEMOBUS/Modbus communications. When
you connect a communication option to the drive, the Run Command source gives priority to the communications option.
bit 6
Multi-function input 3
bit 7
Multi-function input 4
bit 8
Multi-function input 5
bit 9
Multi-function input 6
bit A
Multi-function input 7
bit B
Multi-function input 8
bit C - F
Reserved
0002
Frequency Reference
o1-03 [Frequency Display Unit Selection]
(unsigned) sets the units.
0003
Output voltage gain
Units: 0.1 %
Setting range: 20 (2.0%) to 2000 (200.0%), the default value at energize: 1000 (100.0%)
0004
Torque reference/torque limit (0.1% signed)
0005
Torque compensation (0.1% signed)
0006
PID setpoint (0.01% signed)
0007
Setting for the multi-function analog monitor output terminal 1 (10 V/4000 H)
0008
Setting for the multi-function analog monitor output terminal 2 (10 V/4000 H)
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...