YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
327
Code
Name
Causes
Possible Solutions
oFA10, oFA11
Option Card Error Occurred at
Option Port CN5-A
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA12 to
oFA17
Option Card Connection Error (CN5-
A)
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA30 to
oFA43
Communication Option Card
Connection Error (CN5-A)
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFb00
Option Not Compatible with Port
The option card connected to connector CN5-B is not
compatible.
Connect the option card to the correct connector.
Note:
DO-A3, AO-A3, PG-B3, and PG-X3 options can connect to
connector CN5-B. Use connector CN5-C when connecting only
one encoder option card.
Note:
•
Do a Fault Reset to clear the fault.
•
Fault trace is not available for this fault.
Code
Name
Causes
Possible Solutions
oFb01
Option Fault/Connection Error
The option card connected to connector CN5-B was
changed during operation.
1.
De-energize the drive.
2.
Refer to the option card manual and correctly connect the
option card to the connector on the drive.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFb02
Duplicate Options
The same option cards or the same type of option
cards are connected to connectors CN5-A, B, and C.
Connect the option card to the correct connector.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFb03 to oFb11
Option Card Error Occurred at
Option Port CN5-B
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFb12 to oFb17
Option Card Error Occurred at
Option Port CN5-B
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...