YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
681
■
b3-18: Speed Est Retry Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-18
(01F1)
Expert
Speed Est Retry Detection
Time
Sets the length of time that the drive will wait to retry Speed Estimation Speed Search when too
much current flow stopped the Speed Search.
0.10 s
(0.00 - 1.00 s)
When the current is more than the level set in
b3-17 [Speed Est Retry Current Level]
during the time set in
b3-18
, the
drive tries speed search again.
■
b3-19: Speed Search Restart Attempts
No.
(Hex.)
Name
Description
Default
(Range)
b3-19
(01F2)
Speed Search Restart
Attempts
Sets the number of times to restart Speed Search if Speed Search does not complete.
3 times
(0 - 10 times)
If the drive does the number of Speed Search restarts set in this parameter, it will trigger an
SEr [Speed Search Retries
Exceeded]
error.
■
b3-24: Speed Search Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
b3-24
(01C0)
Speed Search Method
Selection
Sets the Speed Search method when you start the motor or when you return power after a momentary
power loss.
2
(1, 2)
Note:
•
The default setting is different for different control methods.
–
A1-02 = 0, 2 [Control Method Selection = V/f, OLV]
: 2
–
A1-02 = 1 [CL-V/f]
: 1
–
A1-02 = 8 [EZOLV]
and
E9-01 = 0 [Motor Type Selection = Induction (IM)]
: 2
–
A1-02 = 8
and
E9-01 ≠ 0
: 1
•
Set
b3-24 = 1
. If
b3-24 = 2
, the drive will detect
oPE08 [Parameter Selection Error]
.
Set
b3-01 = 1 [Speed Search at Start Selection = Enabled]
to do Speed Search at start. Set
L2-01 = 1 [Power Loss
Ride Through Select = Enabled for L2-02 Time]
to do Speed Search after you restore power after a momentary power
loss.
1 : Speed Estimation
The drive uses the residual voltage from a short baseblock time to estimate the motor speed.
If there is not sufficient residual voltage, then the drive will inject DC current into the motor to estimate the motor
speed.
2 : Current Detection 2
The drive will inject DC current into the motor to estimate motor speed.
■
b3-25: Speed Search Wait Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-25
(01C8)
Expert
Speed Search Wait Time
Sets the length of time the drive will wait to start the Speed Search Retry function.
0.5 s
(0.0 - 30.0 s)
If the drive detects these faults during speed search, increase the setting value:
•
oC [Overcurrent]
•
ov [Overvoltage]
•
SEr [Speed Search Retries Exceeded]
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...