350
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Code
Name
Causes
Possible Solutions
When
A1-02 = 5 to 7 [Control Methods for PM
Motors]
, you used these parameter settings:
•
E5-09 = 0.0 [PM Back-EMF Vpeak (mV/(rad/s))
= 0.0 mV/(rad/s)]
•
E5-24 = 0.0 [PM Back-EMF L-L Vrms (mV/rpm)
= 0.0 mV/min
-1
]
Set
E5-09
or
E5-24
to the correct value.
When
A1-02 = 5 to 7
, you set
E5-09 ≠ 0
and
E5-24 ≠
0
.
Set
E5-09 = 0
or
E5-24 = 0
.
When
A1-02 = 6 [PM Advanced Open Loop Vector]
,
you used these parameter settings:
•
n8-57 = 0 [HFI Overlap Selection = Disabled]
•
You set
E1-09 [Minimum Output Frequency]
< the
5% value of
E1-06
.
Correct the parameter settings.
When
A1-02 = 6
, you set these parameters:
•
n8-35 = 0 [Initial Pole Detection Method = Pull-
in]
•
n8-57 = 1 [Enabled]
Correct the parameter settings.
When
A1-02 = 8 [EZOLV]
, you used these parameter
settings:
•
E9-01 = 1, 2 [Motor Type Selection = Permanent
Magnet (PM), Synchronous Reluctance (SynRM)]
•
b3-24 = 2 [Speed Search Method Selection =
Current Detection 2]
When
E9-01 = 1 or 2
, set
b3-24 = 1 [Speed Estimation]
.
Code
Name
Causes
Possible Solutions
oPE09
PID Control Selection Fault
These parameters are set at the same time:
•
b5-15 ≠ 0.0 [PID Sleep Function Start Level ≠ 0.0
Hz]
•
b1-03 = 2, 3 [Stopping Method Selection = DC
Injection Braking to Stop, Coast to Stop with
Timer]
•
Set
b5-15 ≠ 0.0
.
•
Set
b1-03 = 0, 1 [Ramp to Stop, Coast to Stop]
.
These parameters are set at the same time:
•
b5-01 = 1, 2 [Enabled (Standard), Enabled (D =
Feedforward)]
•
d2-02 ≠ 0.0 [Frequency Reference Lower Limit ≠
0.0%]
Correct the parameter settings.
These parameters are set at the same time:
•
b5-01 = 1, 2 [Enabled (Standard), Enabled (D =
Feedforward)]
•
b5-11 = 1 [PID Output Reverse Selection =
Negative Output Accepted]
Correct the parameter settings.
These parameters are set at the same time:
•
b5-01 = 3, 4 [Trim (Fref+PID Out, D = Fdbk),
Trim (Fref+PID Out, D = FeedFwd)]
•
d2-02 ≠ 0.0
has been set.
Correct the parameter settings.
Note:
The drive detects this error if the PID control function selection is incorrect.
(When
b5-01 = 1 to 4 [PID Mode Setting = PID Control Enabled]
)
Code
Name
Causes
Possible Solutions
oPE10
V/f Data Setting Error
The parameters that set the V/f pattern do not satisfy
these conditions:
•
For motor 1:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤
E1-04 [Minimum Output Frequency ≤ Mid Point A
Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
•
For motor 2:
E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤
E3-04 [Minimum Output Frequency ≤ Mid Point A
Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
Set the parameters correctly to satisfy the conditions.
Code
Name
Causes
Possible Solutions
oPE11
Carrier Frequency Setting Error
These parameters are set at the same time:
•
C6-05 > 6 [Carrier Freq Proportional Gain > 6]
•
C6-04 > C6-03 [Carrier Frequency Lower Limit
> Carrier Frequency Upper Limit]
Note:
When
C6-05 < 7
,
C6-04
becomes disabled. The
drive sets the carrier frequency to the value set to
C6-03
.
C6-02 to C6-05
settings are not in the applicable
setting range.
Set
C6-02 to C6-05
correctly.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...