12.2 A: Initialization Parameters
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
657
■
A1-12: Bluetooth ID
No.
(Hex.)
Name
Description
Default
(Range)
A1-12
(1564)
Bluetooth ID
Sets the password necessary to use Bluetooth to control the drive with a smartphone or tablet.
-
(0000 - 9999)
◆
A2: User Parameters
You can register frequently used parameters and recently changed parameters here to access them quickly. You can
show the registered parameters in [User Custom Parameters] in the main menu.
■
A2-01 to A2-32: User Parameters 1 to 32
No.
(Hex.)
Name
Description
Default
(Range)
A2-01 to A2-32
(0106 - 0125)
User Parameters 1 to 32
You can select a maximum of 32 parameters for the drive and set them to parameters
A2-01 to A2-32
.
The [User Parameters] section of the keypad main menu shows the set parameters. You can
immediately access these set parameters.
Parameters in General-
Purpose Setup Mode
(Determined by A1-06)
Note:
•
Settings for
A2-01 to A2-32
change when the
A1-06 [Application Preset]
value changes.
•
You must set
A1-01 = 1 [Access Level Selection = User Parameters]
to access parameters
A2-01 to A2-32
.
•
When
A1-07 = 1 or 2 [DriveWorksEZ Function Selection = DWEZ Enabled or Enabled/Disabled wDigital Input]
, the drive saves
qx-xx
[DriveWorksEZ Parameters]
to
A2-01 to A2-32
.
The drive saves these parameters to
A2-01 to A2-32
.
•
The drive saves a maximum of 32 parameters.
Note:
Set
A1-01 = 2 [Advanced Level]
or
A1-01 = 3 [Expert Level]
to register the necessary parameters.
•
The drive automatically saves changed parameters to
A2-17 to A2-32
.
Note:
Set
A2-33 = 1 [User Parameter Auto Selection = Enabled]
.
■
A2-33: User Parameter Auto Selection
No.
(Hex.)
Name
Description
Default
(Range)
A2-33
(0126)
User Parameter Auto
Selection
Sets the automatic save feature for changes to parameters
A2-17 to A2-32 [User Parameters 17 to
32]
.
Determined by A1-06
(0, 1)
0 : Disabled: Manual Entry Required
Set User Parameters manually.
1 : Enabled: Auto Save Recent Parms
The drive automatically registers changed parameter
A2-17 to A2-32
. The drive automatically saves the most recently
changed parameter to
A2-17
, and saves a maximum of 16 parameters. After the drive registers 16 parameters, when
you save a new parameter, the drive will remove a parameter from the User Parameter list to make space for the new
parameter. The drive removes parameters with First In, First Out.
You can show the registered parameters in [User Custom Parameters] in the main menu.
Note:
In General-Purpose Setup Mode, the drive registers parameters starting with
A2-27
because the drive registers parameters
A2-26
and lower
by default.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...