Setting Value
Function
Description
Ref.
15
Frequency Detection 3
The terminal deactivates when the output frequency is higher than the value of
“
L4-03 [Speed Agree Detection Level
(+/-)]
+
L4-04 [Speed Agree Detection Width (+/-)]
”
. After the terminal deactivates, the terminal stays off until the
output frequency is at the value of
L4-03
.
Note:
•
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
•
The drive outputs the motor speed status when
A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]
.
ON : The output frequency is less than the value of
L4-03
or it is not higher than the value of
L4-03
+
L4-04
.
OFF : The output frequency is higher than the value of
L4-03
+
L4-04
.
16
Frequency Detection 4
The terminal activates when the output frequency is higher than the value of
L4-03 [Speed Agree Detection Level
(+/-)]
. After the terminal activates, the terminal stays on until the output frequency is at the value of
L4-03
-
L4-04
.
Note:
•
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
•
The drive outputs the motor speed status when
A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]
.
ON : The output frequency is higher than the value of
L4-03
.
OFF : The output frequency is less than the value of
“
L4-03
-
L4-04
”
, or it is not higher than the value of
L4-03
.
17
Torque Detection 1 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with
L6-02 [Torque Detection Level 1]
, or the level
is less than the torque value set with
L6-02 [Torque Detection Level 1]
for longer than the time set with
L6-03 [Torque
Detection Time 1]
.
18
Torque Detection 2 (N.
O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than the torque value set with
L6-05 [Torque Detection Level 2]
, or the level is
less than the torque value set with
L6-05 [Torque Detection Level 2]
for longer than the time set with
L6-06 [Torque
Detection Time 2]
.
19
Torque Detection 2 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with
L6-05 [Torque Detection Level 2]
, or the level
is less than the torque value set with
L6-05 [Torque Detection Level 2]
for longer than the time set with
L6-06 [Torque
Detection Time 2]
.
1A
During reverse
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
1B
During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
1C
Motor 2 Selected
The terminal activates when motor 2 is selected.
ON : Motor 2 Selection
OFF : Motor 1 Selection
1D
During Regeneration
The terminal activates on when the motor is regenerating.
ON : Motor is regenerating.
OFF : Motor is operating or stopped.
1E
Executing Auto-Restart
The terminal activates when the Auto Restart function is trying to restart after a fault.
1F
Motor Overload Alarm
(oL1)
The terminal activates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
20
Drive Overheat Pre-
Alarm (oH)
The terminal activates when the drive heatsink temperature is at the level set with
L8-02 [Overheat Alarm Level]
.
21
Safe Torque OFF
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and
when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety stop state
OFF : Safety circuit fault or RUN/READY
22
Mechanical Weakening
Detection
The terminal activates when the drive detects mechanical weakening.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...