12.2 A: Initialization Parameters
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
647
4 : HVAC Fan
The drive automatically sets the parameters in
for an HVAC fan application.
Table 12.10 Best Parameter Settings for HVAC Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Disabled
b1-17
Run Command at Power Up
1: Accept Existing RUN Command
C6-01
Normal / Heavy Duty Selection
1: Normal Duty Rating
C6-02
Carrier Frequency Selection
3: 8.0 kHz
H2-03
Terminal M5-M6 Function Selection
39: Watt Hour Pulse Output
L2-01
Power Loss Ride Through Select
2: Enabled while CPU Power Active
L8-03
Overheat Pre-Alarm Selection
4: Operate at Reduced Speed (L8-19)
L8-38
Carrier Frequency Reduction
2: Enabled for All Speeds
The drive saves the parameters in
as user parameters.
Table 12.11 Parameters Saved as User Parameters with the HVAC Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
b1-01
Frequency Reference Selection 1
A2-02
b1-02
Run Command Selection 1
A2-03
b1-03
Stopping Method Selection
A2-04
b1-04
Reverse Operation Selection
A2-05
C1-01
Acceleration Time 1
A2-06
C1-02
Deceleration Time 1
A2-07
C6-02
Carrier Frequency Selection
A2-08
d2-01
Frequency Reference Upper Limit
A2-09
d2-02
Frequency Reference Lower Limit
A2-10
E1-03
V/f Pattern Selection
A2-11
E1-04
Maximum Output Frequency
A2-12
E2-01
Motor Rated Current (FLA)
A2-13
H3-11
Terminal A2 Gain Setting
A2-14
H3-12
Terminal A2 Bias Setting
A2-15
L2-01
Power Loss Ride Through Select
A2-16
o4-12
kWh Monitor Initialization
5 : Air Compressor
The drive automatically sets the parameters in
for an air compressor application.
Table 12.12 Best Parameter Settings for Air Compressor Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Disabled
C1-01
Acceleration Time 1
5.0 s
C1-02
Deceleration Time 1
5.0 s
C6-01
Normal / Heavy Duty Selection
0: Heavy Duty Rating
E1-03
V/f Pattern Selection
F: Custom
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...