L3-40: Current Limit S-Curve @ Acc/Dec
No.
(Hex.)
Name
Description
Default
(Range)
L3-40
(11D4)
Current Limit S-Curve @
Acc/Dec
Sets the function to enable and disable the best S-curve characteristic used for current-limited
acceleration.
0
(0, 1)
Makes the best motor acceleration rate for start up. If you set this parameter to 1, it will make acceleration smoother,
but it can also increase the acceleration time to be longer than the set time. If the drive detects
oC [Overcurrent]
faults
immediately after acceleration starts, set this parameter.
0 : No
1 : Yes
Note:
Set
L3-01 = 3 [Stall Prevention during Accel = Current Limit Method]
to enable this function.
◆
L4: Speed Detection
L4 parameters
set the output of signals to the MFDO terminals, for example frequency agree and speed detection. The
drive detects motor speed in CLV or CLV/PM control methods.
■
L4-01: Speed Agree Detection Level
No.
(Hex.)
Name
Description
Default
(Range)
L4-01
(0499)
Speed Agree Detection
Level
Sets the level to detect speed agree or motor speed.
Determined by A1-02
(Determined by A1-02)
Sets the level to detect speed agree or motor speed when
H2-01 to H2-03 = 2, 3, 4, 5 [MFDO Function Select =
Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2]
.
■
L4-02: Speed Agree Detection Width
No.
(Hex.)
Name
Description
Default
(Range)
L4-02
(049A)
Speed Agree Detection
Width
Sets the width to detect speed agree or motor speed.
Determined by A1-02
(Determined by A1-02)
Sets the width to detect speed agree or motor speed when
H2-01 to H2-03 = 2, 3, 4, 5 [MFDO Function Select =
Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2]
.
■
L4-03: Speed Agree Detection Level (+/-)
No.
(Hex.)
Name
Description
Default
(Range)
L4-03
(049B)
Speed Agree Detection
Level (+/-)
Sets the level to detect speed agree or motor speed.
Determined by A1-02
(Determined by A1-02)
Sets the speed agree detection level or motor speed detection level when
H2-01 to H2-03 = 13, 14, 15, 16 [MFDO
Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3, Frequency Detection 4]
.
■
L4-04: Speed Agree Detection Width (+/-)
No.
(Hex.)
Name
Description
Default
(Range)
L4-04
(049C)
Speed Agree Detection
Width (+/-)
Sets the width to detect speed agree or motor speed.
Determined by A1-02
(Determined by A1-02)
Sets the width to detect speed agree or motor speed when
H2-01 to H2-03 = 13, 14, 15, 16 [MFDO Function
Selection = Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3, Frequency Detection 4]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...