SIEPC71061737B GA800 Drive Technical Reference
863
■
18: Torque Detection 2 (N.O.)
Setting Value
Function
Description
18
Torque Detection 2 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
ON : The output current/torque is more than the torque value set with
L6-05 [Torque Detection Level
2]
, or the level is less than the torque value set with
L6-05
for longer than the time set with
L6-06
[Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than the detection level of
L6-05
for longer than the time set in
L6-06
.
•
Refer to
“
L6: Torque Detection
”
for more information.
■
19: Torque Detection 2 (N.C.)
Setting Value
Function
Description
19
Torque Detection 2 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
OFF : The output current/torque is more than the torque value set with
L6-05 [Torque Detection
Level 2]
, or the level is less than the torque value set with
L6-05
for longer than the time set with
L6-
06 [Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than the detection level of
L6-05
for longer than the time set in
L6-06
.
•
Refer to
“
L6: Torque Detection
”
for more information.
■
1A: During Reverse
Setting Value
Function
Description
1A
During reverse
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
Figure 12.99 Reverse Operation Output Time Chart
■
1B: During Baseblock (N.C.)
Setting Value
Function
Description
1B
During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : The drive is not in baseblock.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...