12.2 A: Initialization Parameters
644
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
No.
(Hex.)
Name
Description
Default
(Range)
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0
(0 - 5)
The drive software contains the application presets shown below. Set
A1-06
to align with the application to let the
drive automatically set the best parameter settings for the selected application. The drive saves parameters frequently
used for the application in parameters
A2-01 to A2-16 [User Parameters 1 to 16]
for easy configuration and reference
in [User Custom Parameters] in the main menu.
•
Water supply pump
•
Conveyor
•
Exhaust fan
•
HVAC fan
•
Air compressor
Note:
•
Before you set
A1-06
, make sure that you set
A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization]
to
initialize parameters.
•
It is not possible to change the
A1-06
value. To set an application preset, first set
A1-03 = 2220
to initialize parameters, then set this
parameter. If initializing all parameters will cause a problem, do not change the settings.
If you set
A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms]
to set parameters to
A2-17 to A2-32 [User
Parameters 17 to 32]
automatically, the drive will reset these parameters when you change the
A1-06
setting.
0 : General-purpose
The drive saves the parameters in
as user parameters.
Table 12.3 Parameters Saved as User Parameters with the General-purpose Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
A1-02
Control Method Selection
A2-02
b1-01
Frequency Reference Selection 1
A2-03
b1-02
Run Command Selection 1
A2-04
b1-03
Stopping Method Selection
A2-05
C1-01
Acceleration Time 1
A2-06
C1-02
Deceleration Time 1
A2-07
C6-01
Normal / Heavy Duty Selection
A2-08
C6-02
Carrier Frequency Selection
A2-09
d1-01
Reference 1
A2-10
d1-02
Reference 2
A2-11
d1-03
Reference 3
A2-12
d1-04
Reference 4
A2-13
d1-17
Jog Reference
A2-14
E1-01
Input AC Supply Voltage
A2-15
E1-03
V/f Pattern Selection
A2-16
E1-04
Maximum Output Frequency
A2-17
E1-05
Maximum Output Voltage
A2-18
E1-06
Base Frequency
A2-19
E1-09
Minimum Output Frequency
A2-20
E1-13
Base Voltage
A2-21
E2-01
Motor Rated Current (FLA)
A2-22
E2-04
Motor Pole Count
A2-23
E2-11
Motor Rated Power
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...