YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
733
■
C5-38: Motor 2 Load Inertia Ratio
No.
(Hex.)
Name
Description
Default
(Range)
C5-38
(0279)
Expert
Motor 2 Load Inertia Ratio
Sets the load inertia ratio for the motor 2 inertia.
1.0
(0.0 - 6000.0)
The drive automatically sets
C5-38
to the value of [Load Inertia Ratio] when you do Inertia Tuning or ASR Tuning.
■
C5-39: ASR Primary Delay Time Const 2
No.
(Hex.)
Name
Description
Default
(Range)
C5-39
(030D)
ASR Primary Delay Time
Const 2
Sets the filter time constant used when the torque reference is output from ASR. Usually it is not
necessary to change this parameter.
0.000 s
(0.000 - 0.500 s)
If you have a load with low rigidity or if oscillation is a problem, increase this setting in 0.01 unit increments.
■
C5-50: Notch Filter Frequency
No.
(Hex.)
Name
Description
Default
(Range)
C5-50
(0B14)
Expert
Notch Filter Frequency
Sets the machine resonance frequency.
0 Hz
(0, or 2 to 100 Hz)
Machine resonance can cause high-frequency noise and vibration during operation. A notch filter can help prevent the
noise and vibration. Notch filters set the resonant frequency of the machine to remove specific vibrational frequency
components caused by machine resonance.
Note:
•
Correctly set the value for the notch filter frequency. If the frequency value is too low for the speed loop response frequency, the speed
control function will not function correctly. Set the frequency to be a minimum of 4 times the speed loop response frequency.
•
Set
C5-50 = 0 [0 Hz]
to disable the notch filter.
■
C5-51: Notch Filter Bandwidth
No.
(Hex.)
Name
Description
Default
(Range)
C5-51
(0B15)
Expert
Notch Filter Bandwidth
Sets the notch width of the notch filter.
1.0
(0.5 - 5.0)
Note:
Set
C5-50 = 0 [Notch Filter Frequency = 0 Hz]
to disable the notch filter.
◆
C6: Duty & Carrier Frequency
C6 parameters
are used to set the selection of drive duty rating, selection of carrier frequency, and upper and lower
limits of carrier frequencies.
■
C6-01: Normal / Heavy Duty Selection
No.
(Hex.)
Name
Description
Default
(Range)
C6-01
(0223)
Normal / Heavy Duty
Selection
Sets the drive duty rating.
1
(0, 1)
0 : Heavy Duty Rating
The overload tolerance is 150% of the rated output current for 60 seconds.
1 : Normal Duty Rating
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...