254
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
■
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
•
If
E2-01 < E2-03 [Motor No-Load Current]
, the drive will detect
oPE02 [Parameter Range Setting Error]
.
•
When the drive model changes, the display units for this parameter also change.
–
0.01 A: models 2004 to 2042, 4002 to 4023
–
0.1 A: models 2056 to 2415, 4031 to 4720
The value set for
E2-01
becomes the reference value for motor protection, the torque limit, and torque control. Enter
the motor rated current shown on the motor nameplate. Auto-Tuning the drive will automatically set
E2-01
to the
value input for
“
Motor Rated Current
”
.
■
E5-03: PM Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E5-03
(032B)
PM Motor Rated Current
(FLA)
Sets the PM motor rated current (FLA).
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
•
0.01 A: models 2004 to 2042, 4002 to 4023
•
0.1 A: models 2056 to 2415, 4031 to 4720
After you do these types of Auto-Tuning, the drive automatically will set
E5-03
to the value input for
“
PM Motor
Rated Current
”
:
•
PM Motor Parameter Settings
•
PM Stationary Auto-Tuning
•
PM StaTun for Stator Resistance
•
PM Rotational Auto-Tuning
■
E9-06: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E9-06
(11E9)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by E9-01 and
o2-04
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
•
0.01 A: models 2004 to 2042, 4002 to 4023
•
0.1 A: models 2056 to 2415, 4031 to 4720
The value set for
E9-06
becomes the reference value for motor protection. Enter the motor rated current shown on the
motor nameplate. Auto-Tuning the drive will automatically set
E9-06
to the value input for
“
Motor Rated Current
”
.
■
L1-01: Motor Overload (oL1) Protection
No.
(Hex.)
Name
Description
Default
(Range)
L1-01
(0480)
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors.
Determined by A1-02
(0 - 6)
This parameter enables and disables the motor overload protection with electronic thermal protectors.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...