6.3 MEMOBUS/Modbus Communications
282
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Byte
Command Message
Response Message (when normal)
Response Message (when there is a fault)
Setting Data
(Hex.)
Setting Data
(Hex.)
Setting Data
(Hex.)
10
Holding register
1 data
Upper
17
-
-
11
Lower
70
-
-
12
Holding register
2 No.
Upper
00
-
-
13
Lower
04
-
-
14
Holding register
2 data
Upper
05
-
-
15
Lower
DC
-
-
16
CRC-16
Upper
55
-
-
17
Lower
59
-
-
Note:
The number of bytes set in the command message set the data quantity × 2 during the command message.
◆
Enter Command
When you use MEMOBUS/Modbus communications to write parameters from the PLC to the drive, the
H5-11
[Comm ENTER Command Mode]
setting sets the function to enable these parameters from the Enter command. This
section gives information about the Enter command.
■
Types of Enter Commands
The drive supports the two Enter commands shown in
Write 0 to register number 0900 or 0910 (Hex.) to enable the Enter command. You can only write to these registers. If
you read to these registers, it will cause an error.
Table 6.9 Types of Enter Commands
Register No.
(Hex.)
Description
0900
When you write parameter data to the EEPROM, you will enable the data on the RAM at the same time.
This process saves the parameter changes until you de-energize the drive.
0910
This updates the data on the RAM, but does not write data to the EEPROM.
This process saves the parameter changes until you de-energize the drive.
Note:
•
You can write the EEPROM to the drive a maximum of 100,000 times. Do not frequently execute the Enter command (0900 (Hex.)) that is
written to EEPROM. The Enter command register is write-only. If this register is read, it will cause a Register Number Error (02 (Hex.)).
•
When the command data or broadcast message is transmitted to the drive, the Enter command is not necessary.
■
Functions of the Enter Command when Replacing a Previous Generation Drive
When you replace a previous generation Yaskawa drive with this product, you must set the Enter command function
for this product the same as the previous product. The Enter command function is different for Yaskawa G7, F7-
series, and V7-series drives.
Use
H5-11
to set the Enter command function:
•
When replacing G7 and F7 series drives, set
H5-11 = 0 [ENTER Command Required]
.
•
When replacing V7 series drives, set
H5-11 = 1 [ENTER Command Not Required]
.
•
When replacing 1000-series drives, set
H5-11
to the same value as the drive you replaced.
Table 6.10 Enter Command Function Differences
H5-11 Settings
H5-11 = 0
H5-11 = 1
The drive you replaced
G7, F7
V7
Time when the parameter settings are enabled
When the drive receives the Enter command from the
master
When you change the parameter settings
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...