798
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Coded Output (Binary)
Description
DO-A3 Terminal Block TB2
Terminal P1-PC
Terminal P2-PC
Terminal P3-PC
Terminal P4-PC
4
oH, oH1 [Heatsink
Overheat]
0
0
1
0
5
oS [Overspeed]
1
0
1
0
6
Not used
0
1
1
0
7
rr [Dynamic Braking
Transistor Fault], rH
[Braking Resistor Overheat]
1
1
1
0
8
External fault [EF1 to EF8]
0
0
0
1
9
CPFxx, oFAxx, oFbxx,
oFCxx [Drive Hardware
Fault]
1
0
0
1
A
oL1 [Motor Overload]
0
1
0
1
B
Not used
1
1
0
1
C
Uv1, Uv2 [Undervoltage],
Uv3 [Soft Charge
Answerback Fault]
0
0
1
1
D
dEv [Speed Deviation]
1
0
1
1
E
PGo [Encoder (PG)
Feedback Loss]
0
1
1
1
F
Not used
1
1
1
1
*1
The
“
xx
”
characters are different for different faults.
■
Digital Output Card Selection
Refer to
“
H2: Multi-function Digital Output
”
for more information about the functions that output from the terminals
when
F5-09 = 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to F5-08)]
. Use
F5-01 to F5-08
to set the
output items.
No.
Name
Setting Range
Default
F5-01
Terminal P1-PC Function Select
0 - 192
0: During Run
F5-02
Terminal P2-PC Function Select
0 - 192
1: Zero Speed
F5-03
Terminal P3-PC Function Select
0 - 192
2: Speed Agree 1
F5-04
Terminal P4-PC Function Select
0 - 192
4: Frequency Detection 1
F5-05
Terminal P5-PC Function Select
0 - 192
6: Drive Ready
F5-06
Terminal P6-PC Function Select
0 - 192
37: During Frequency Output
F5-07
Terminal M1-M2 Function Select
0 - 192
F: Not Used
F5-08
Terminal M3-M4 Function Select
0 - 192
F: Not Used
■
F5-01: Terminal P1-PC Function Select
No.
(Hex.)
Name
Description
Default
(Range)
F5-01
(0399)
Terminal P1-PC Function
Select
Sets the function of terminal P1-PC on the DO-A3 option. Set
F5-09 = 2 [DO-A3 Output Mode
Selection = Programmable (F5-01 to F5-08)]
to enable this function.
0
(0 - 1A7)
■
F5-02: Terminal P2-PC Function Select
No.
(Hex.)
Name
Description
Default
(Range)
F5-02
(039A)
Terminal P2-PC Function
Select
Sets the function of terminal P2-PC on the DO-A3 option. Set
F5-09 = 2 [DO-A3 Output Mode
Selection = Programmable (F5-01 to F5-08)]
to enable this function.
1
(0 - 1A7)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...