880
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Note:
When you set this function, it will disable the setting value of
b2-02 [DC Injection Braking Current]
.
Figure 12.106 DC Injection Braking Current through Analog Input
■
7: Torque Detection Level
Setting Value
Function
Description
7
Torque Detection Level
Enters a signal to adjust the overtorque/undertorque detection level.
When
A1-02 = 0, 1, 5 [Control Method Selection = V/f, CL-V/f, OLV/PM]
, the drive rated current is 100%. When
A1-
02 = 2, 3, 4, 6, 7, 8 [OLV, CLV, AOLV, AOLV/PM, CLV/PM, EZOLV]
, the motor rated torque is 100%.
Note:
Use this function with
L6-01 [Torque Detection Selection 1]
. This parameter functions as an alternative to
L6-02 [Torque Detection Level 1]
.
■
8: Stall Prevent Level During Run
Setting Value
Function
Description
8
Stall Prevent Level During
Run
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
Note:
The Stall Prevent Level During Run is based on the smaller of these two values:
•
Analog input value of MFAI terminal
•
L3-06 [Stall Prevent Level during Run]
Figure 12.107 Stall Prevention Level during Run with Analog Input
■
9: Output Frequency Lower Limit
Setting Value
Function
Description
9
Output Frequency Lower
Limit
Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.
■
B: PID Feedback
Setting Value
Function
Description
B
PID Feedback
Enter the PID feedback value as a percentage of the maximum output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...