896
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Figure 12.118 Virtual Digital I/O Functional Block Diagram
Note:
•
Refer to H1-xx "MFDI Setting Values" for more information on the virtual digital input setting values.
•
Refer to H2-xx "MFDO Setting Values" for more information on the virtual digital output setting values.
•
Refer to H3-xx "MFAI Setting Values" for more information on the virtual analog input setting values.
•
Refer to H4-xx "MFAO Setting Values" for more information on the virtual analog output setting values.
•
You cannot set
0 [3-Wire Sequence]
and
20 or 2F [External Fault]
to
H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4]
.
•
If the terminal is not used, set
H7-01 to H7-04 = F
. The through mode function is not supported.
•
The virtual I/O function selection and the multi-function input for DI-A3 cannot be used simultaneously.
■
H7-00: Virtual MFIO selection
No.
(Hex.)
Name
Description
Default
(Range)
H7-00
(116F)
Expert
Virtual MFIO selection
Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to operate the
virtual I/O function.
0
(0, 1)
0 : Disabled
1 : Enabled
■
H7-01: Virtual Multi-Function Input 1
No.
(Hex.)
Name
Description
Default
(Range)
H7-01
(1185)
Expert
Virtual Multi-Function Input
1
Sets the function that enters the virtual input set in
H7-10 [Virtual Multi-Function Output 1]
.
F
(1 - 19F)
Note:
Settings
1B [Programming Lockout]
and
11B [!Programming Lockout]
are not available.
■
H7-02: Virtual Multi-Function Input 2
No.
(Hex.)
Name
Description
Default
(Range)
H7-02
(1186)
Expert
Virtual Multi-Function Input
2
Sets the function that enters the virtual input set in
H7-12 [Virtual Multi-Function Output 2]
.
F
(1 - 19F)
Note:
Settings
1B [Programming Lockout]
and
11B [!Programming Lockout]
are not available.
■
H7-03: Virtual Multi-Function Input 3
No.
(Hex.)
Name
Description
Default
(Range)
H7-03
(1187)
Expert
Virtual Multi-Function Input
3
Sets the function that enters the virtual input set in
H7-14 [Virtual Multi-Function Output 3]
.
F
(1 - 19F)
Note:
Settings
1B [Programming Lockout]
and
11B [!Programming Lockout]
are not available.
H7-01
[Virtual Multi-Function
Input 1]
H7-11
[Virtual Output
1 Delay Time]
H7-10
[Virtual Multi-Function
Output 1]
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...