F4-07: Terminal V1 Signal Level
No.
(Hex.)
Name
Description
Default
(Range)
F4-07
(0397)
Terminal V1 Signal Level
Sets the output signal level for terminal V1.
0
(0, 1)
0 : 0 to 10 V
1 : -10 to 10 V
■
F4-08: Terminal V2 Signal Level
No.
(Hex.)
Name
Description
Default
(Range)
F4-08
(0398)
Terminal V2 Signal Level
Sets the output signal level for terminal V2.
0
(0, 1)
0 : 0 to 10 V
1 : -10 to 10 V
◆
F5: Digital Output Option
F5 parameters
set the output mode and function of output signals when you use digital output option card DO-A3.
When you install a DO-A3 to the drive, you can output isolated digital signals to monitor the drive operation status.
•
6 points of photocoupler output (48 V, 50 mA or less)
•
2 points of relay contact output (250 Vac, 30 Vdc: 1 A or less)
Refer to the DO-A3 option manual for more information about how to install, wire, and set the DO-A3 card.
■
Use Parameters to Select Output Modes
Use parameter
F5-09 [DO-A3 Output Mode Selection]
to set signal output from the DO-A3 card.
Table 12.45 Details of F5-09 and the DO-A3 Terminal Output
DO-A3 Terminal Block
DO-A3 Terminal Name
F5-09 = 0 [Predefined
Individual Outputs] (Default)
F5-09 = 1 [Binary Output]
F5-09 = 2 [Programmable (F5-
01 to F5-08)]
TB1
M1-M2
Zero speed detection in progress
During run
Depending on the setting of F5-07
[Terminal M1-M2 Function Select]
M3-M4
During speed agreement
Minor fault (excluding bb
[Baseblock])
Depending on the setting of F5-08
[Terminal M3-M4 Function Select]
TB2
P1-PC
oC [Overcurrent], GF [Ground
Fault]
Coded output
Note:
Refer to
for
details.
Depending on the setting of F5-01
[Terminal P1-PC Function Select]
P2-PC
ov [Overvoltage]
Depending on the setting of F5-02
[Terminal P2-PC Function Select]
P3-PC
oL2 [Drive Overload] or oH2
[Heatsink Overheat]
Depending on the setting of F5-03
[Terminal P3-PC Function Select]
P4-PC
Not used
Depending on the setting of F5-04
[Terminal P4-PC Function Select]
P5-PC
oS [Overspeed]
Zero speed detection in progress
Depending on the setting of F5-05
[Terminal P5-PC Function Select]
P6-PC
oH, oH1 [Heatsink Overheat] or
oL1 [Motor Overload]
During speed agreement
Depending on the setting of F5-06
[Terminal P6-PC Function Select]
Table 12.46 Binary Output [F5-09 = 1]
Coded Output (Binary)
Description
DO-A3 Terminal Block TB2
Terminal P1-PC
Terminal P2-PC
Terminal P3-PC
Terminal P4-PC
0
No fault
0
0
0
0
1
oC [Overcurrent], GF
[Ground Fault]
1
0
0
0
2
ov [Overvoltage]
0
1
0
0
3
oL2 [Drive Overloaded]
1
1
0
0
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...