Gradually increase the setting value when a large quantity of current flows after speed search starts. If you set this
value too high, speed search will not operate correctly.
■
b3-56: InverseRotationSearch WaitTime
No.
(Hex.)
Name
Description
Default
(Range)
b3-56
(3126)
InverseRotationSearch
WaitTime
Sets the wait time until the drive starts inverse rotation search after it completes forward search when
you do inverse rotation search during Current Detection Speed Search.
Determined by o2-04
(0.1 - 5.0 s)
■
b3-61: Init Magnet Pole Estimation Gain
No.
(Hex.)
Name
Description
Default
(Range)
b3-61
(1B96)
Expert
Init Magnet Pole Estimation
Gain
Adjusts the Initial Pole Detection response gain when
A1-02 = 6 [Control Method Selection = AOLV/
PM]
. Set
b3-61 > 0.0
for a general IPM motor.
5.0
(-20.0 - +20.0)
Use this when
n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection]
. Adjusts the response gain for
Initial Pole Detection. Specify a positive value for an ordinary motor. The drive sets this value automatically when
High Frequency Injection Tuning completes correctly.
◆
b4: Timer Function
The drive uses timers to delay activating and deactivating MFDO terminals.
Timers prevent sensors and switches from making chattering noise.
There are two types of timers:
•
Timers that set a delay for timer inputs and timer outputs.
These timers delay activating and deactivating of the MFDIs and MFDOs.
To enable this function, set
H1-xx = 18 [MFDI Function Select = Timer Function], and set H2-01 to H2-03 = 12
[MFDO Function Select = Timer Output]
.
•
Timers that set a delay to activate and deactivate MFDO terminals.
These timers delay activating and deactivating MFDO terminals.
To enable this function, set delay times in parameters
b4-03 to b4-08
.
■
Timer Function Operation
•
Timers that Set a Delay for Timer Inputs and Timer Outputs
Triggers timer output if the timer input is active for longer than the time set in
b4-01 [Timer Function ON-Delay
Time]
. Triggers timer output late for the time set in
b4-02 [Timer Function OFF-Delay Time]
.
shows
an example of how the timer function works.
Figure 12.32 Example of Timer Function Operation
•
Setting On/Off-delay Time for MFDO
uses H2-01 terminals to show an example of how the timer function works. Use
b4-03 [Terminal M1-
M2 ON-Delay Time]
and
b4-04 [Terminal M1-M2 OFF-Delay Time]
to set this function.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...