934
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an
oL3
and operation
stops.
5 : UL @ Speed Agree - Alarm only
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a
UL3 [Undertorque Detection 1]
and operation continues.
6 : UL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a
UL3
and operation
continues.
7 : UL @ Speed Agree - Fault
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a
UL3
and operation stops.
8 : UL @ RUN - Fault
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a
UL3
and operation
stops
■
L6-02: Torque Detection Level 1
No.
(Hex.)
Name
Description
Default
(Range)
L6-02
(04A2)
Torque Detection Level 1
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
Note:
•
Set the torque detection level as a percentage of the drive rated output current in all control methods to set the mechanical weakening
detection level.
•
You can also use an analog input terminal to supply the torque detection level. To enable this function, set
H3-xx = 7 [MFAI Function Select
= Overtorque/Undertorque DetectLvl]
. If you set
L6-02
and
H3-x = 7
, the analog input is most important and the drive disables
L6-02
.
■
L6-03: Torque Detection Time 1
No.
(Hex.)
Name
Description
Default
(Range)
L6-03
(04A3)
Torque Detection Time 1
Sets the detection time for Overtorque/Undertorque Detection 1.
0.1 s
(0.0 - 10.0 s)
■
L6-04: Torque Detection Selection 2
No.
(Hex.)
Name
Description
Default
(Range)
L6-04
(04A4)
Torque Detection Selection 2
Sets the speed range that detects overtorque and undertorque and the operation of drives (operation
status) after detection.
0
(0 - 8)
The drive detects overtorque if the motor current or output torque is more than the level set in
L6-05 [Torque
Detection Level 2]
for the length of time set in
L6-06 [Torque Detection Time 2]
. The drive detects undertorque if the
motor current or output torque is less than the level set in
L6-05
for the length the time set in
L6-06
.
0 : Disabled
The drive will not detect overtorque or undertorque.
1 : oL @ Speed Agree - Alarm only
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not occur
during acceleration/deceleration. The drive outputs an
oL4 [Overtorque Detection 2]
and operation continues.
2 : oL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an
oL4
and operation
continues.
3 : oL @ Speed Agree - Fault
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...