YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
943
■
L8-11: Heatsink Fan Off-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-11
(04B7)
Heatsink Fan Off-Delay
Time
Sets the length of time that the drive will wait before it stops the cooling fan after it cancels the Run
command when
L8-10 = 0 [Heatsink Cooling Fan Ope Select = Dur Run (OffDly)]
.
60 s
(0 - 300 s)
■
L8-12: Ambient Temperature Setting
No.
(Hex.)
Name
Description
Default
(Range)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
40 °C
(-10 °C - +50 °C)
The drive automatically adjusts the drive rated current to the best value as specified by the set temperature. Set the
ambient temperature of the area where you install the drive to a value that is more than the drive rating.
Refer to
Derating Depending on Ambient Temperature on page 450
for information about derating depending on
ambient temperature.
■
L8-15: Drive oL2 @ Low Speed Protection
No.
(Hex.)
Name
Description
Default
(Range)
L8-15
(04BB)
Drive oL2 @ Low Speed
Protection
Sets the function to decrease drive overload at low speeds to prevent damage to the main circuit
transistor during low speed operation (at 6 Hz or slower) to prevent
oL2 [Drive Overloaded]
.
1
(0, 1)
Note:
Contact Yaskawa or your nearest sales representative for consultation before disabling this function at low speeds. Frequent operation of
drives under conditions of high output current in low speed ranges may shorten the service life of the drive IGBT due to heat stress.
0 : Disabled (No Additional Derate)
The drive does not decrease the overload protection level.
1 : Enabled (Reduced oL2 Level)
When the drive detects
oL2
during low speed operation, it automatically decreases the overload detection level.
At zero speed, the drive derates the overload by 50%.
■
L8-18: Software Current Limit Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-18
(04BE)
Software Current Limit
Selection
Set the software current limit selection function to prevent damage to the main circuit transistor
caused by too much current.
0
(0, 1)
0 : Disabled
When the output current is at the software current limit value, the drive does not restrict the output voltage.
Note:
The drive may detect an
oC [Overcurrent]
when loads are particularly heavy or the acceleration time is particularly short.
1 : Enabled
When the output current is at the software current limit value, the drive decreases output voltage to decrease output
current.
When the output current decreases to the software current limit level, the drive starts usual operation.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...