450
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Model
Rated Current (A)
Heavy Duty Rating (HD)
Parameter C6-01 = 0
Normal Duty Rating (ND)
Parameter C6-01 = 1
2 kHz
(2 kHz)
4 kHz
(-)
6 kHz
(5 kHz)
8 kHz
(8 kHz)
10 kHz
(10 kHz)
12 kHz
(12.5 kHz)
2 kHz
(2 kHz)
4 kHz
(-)
6 kHz
(5 kHz)
8 kHz
(8 kHz)
10 kHz
(10 kHz)
12 kHz
(12.5 kHz)
4023
18.0
15.6
13.2
10.8
8.4
6.0
21.0
18.3
15.5
12.7
9.9
7.0
4031
27.2
23.5
19.8
16.1
12.4
8.7
27.0
23.3
19.6
16.0
12.3
8.6
4038
34.7
30.1
25.5
20.8
16.2
11.6
34.0
30.9
26.2
21.4
16.6
11.9
4044
34.0
34.0
32.1
26.2
20.4
14.6
40.0
37.8
32.3
26.8
21.3
15.8
4060
40.0
40.0
37.4
29.6
21.7
13.9
52.0
44.3
36.7
29.0
21.3
13.6
4075
52.0
52.0
49.0
40.1
31.2
22.3
65.0
60.9
51.4
42.0
32.5
23.0
4089
65.0
65.0
61.3
50.1
39.0
27.9
77.0
72.9
61.7
50.6
39.4
28.2
4103
77.0
77.0
72.6
59.4
46.2
33.0
96.0
93.6
79.4
65.1
50.9
36.6
4140
96.0
90.2
73.0
55.7
38.4
-
124.0
101.1
78.0
54.9
31.9
-
4168
124.0
116.6
94.2
71.9
49.6
-
156.0
131.7
107.4
83.1
58.8
-
4208
156.0
146.6
118.6
90.5
62.4
-
180.0
143.2
106.5
69.7
33.0
-
4250
180.0
169.2
136.8
104.4
72.0
-
240.0
199.4
158.7
118.1
77.4
-
4302
240.0
225.6
182.4
139.2
96.0
-
302.0
252.2
202.3
152.5
102.6
-
4371
302.0
283.9
229.5
175.2
120.8
-
361.0
297.2
233.5
169.7
105.9
-
4414
361.0
339.3
274.4
209.4
144.4
-
414.0
347.6
281.1
214.7
148.3
-
4477
414.0
310.5
-
-
-
-
477.0
312.6
-
-
-
-
4568
477.0
357.8
-
-
-
-
515.0
337.5
-
-
-
-
4605
515.0
386.3
-
-
-
-
605.0
406.7
-
-
-
-
4720
605.0
453.8
-
-
-
-
720.0
484.0
-
-
-
-
*1
The upper values are for
A1-02 = 6 [Control Method Selection = AOLV/PM]
. The values in parenthesis are for
A1-02 = 4 [ALOV]
.
◆
Derating Depending on Ambient Temperature
When you install drives in a place where ambient temperatures are higher than the rated conditions or install drives
side-by-side in the enclosure panel, set
L8-12 [Ambient Temperature] and L8-35 [Installation Method Selection]
.
Derate the output current as specified in
.
No.
(Hex.)
Name
Description
Default
(Range)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
40 °C
(-10 °C - +50 °C)
No.
(Hex.)
Name
Description
Default
(Range)
L8-35
(04EC)
Installation Method
Selection
Sets the type of drive installation.
Determined by the drive
(0 - 3)
0 : IP20/OpenChassis Enc/Ex Heatsink
You can use the drive within the rated output current range of -10 °C to 50 °C 100%. Use this setting to install an
IP20/UL Open Type drive or when the heatsink (cooling fin) is outside the enclosure panel.
Make sure that there is 30 mm (1.18 in) minimum of space between drives or between the drive and side of the
enclosure panel.
1 : Side-by-Side Mounting
Derates the drive rated output current from "-10 °C to 30 °C 100%" to "30 °C 100%" to "50 °C 70%". Use this setting
to install more than one drive Side-by-Side.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...