Figure 12.28 Current Detection 2 after a Momentary Power Loss
Note:
Once power is restored, the drive will not execute Speed Search until the time set in
b3-05 [Speed Search Delay Time]
has passed. Thus, the
drive will not always start Speed Search although the time set in
L2-03 [Minimum Baseblock Time]
is expired.
If you enter the Run command at the same time as Speed Search, the drive will not do Speed Search until the time set
in
L2-03
is expired. When the value set in
L2-03
<
b3-05
, the drive will use the wait time set in
b3-05
.
Figure 12.29 Speed Search Selection at Start (Current Detection Type)
WARNING!
Sudden Movement Hazard. Do not do Current Detection Speed Search with light loads or a stopped motor. If you do
Auto-Tuning in these conditions, the motor can suddenly accelerate and cause serious injury or death.
Note:
•
You cannot use Current Detection Speed Search with PM motors.
•
If the motor is rotating in reverse, you cannot do Speed Search.
•
If the drive detects
oL1 [Motor Overload]
during Current Detection Speed Search, decrease the value set in
b3-03
.
•
If the drive detects
oC [Overcurrent]
or ov [Overvoltage] during Current Detection Speed Search after the drive recovers from a momentary
power loss, increase the value set in
L2-03
.
■
Speed Estimation
Use this Speed Search function with induction motors. Set
b3-24 = 1 [Speed Search Method Selection = Speed
Estimation]
. This function uses less current and has a shorter search time than other functions. This function lets you
do Speed Search when the motor is rotating in reverse. When you return power after a power loss, the motor will not
suddenly accelerate.
Note:
You cannot do Speed Estimation Speed Search in these conditions:
•
When you operate more than one motor with one drive
•
When you use a high-speed motor (200 Hz or higher)
•
When you use a 1.5 kW or smaller motor.
•
When the motor output is more than 1 frame size smaller than the drive capacity
•
When there is a long wiring distance between the drive and motor
For these conditions, use Current Detection Speed Search.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...