L3-11: Overvoltage Suppression Select
No.
(Hex.)
Name
Description
Default
(Range)
L3-11
(04C7)
Overvoltage Suppression
Select
Sets the overvoltage suppression function.
0
(0, 1)
0 : Disabled
The drive does not adjust the regenerative torque limit or the output frequency. If you apply a regenerative load, the
drive can detect an
ov [Overvoltage]
fault. Use this setting with a dynamic braking option.
1 : Enabled
When a regenerative load increases the DC bus voltage, the drive decreases the regenerative torque limit and
increases the output frequency to prevent
ov
■
L3-17: DC Bus Regulation Level
No.
(Hex.)
Name
Description
Default
(Range)
L3-17
(0462)
DC Bus Regulation Level
Sets the target value for the DC bus voltage when the overvoltage suppression function and the Decel
Stall Prevention function (Intelligent Stall Prevention) are active.
200 V Class: 375 V, 400 V:
750 V
(200 V Class: 150 to 400 V,
400 V Class: 300 to 800 V)
Note:
This value is initialized when
E1-01 [Input AC Supply Voltage]
is changed.
Sets this parameter for any of the following circumstances.
•
L3-11 = 1 [OV Suppression Function Select = Enabled]
.
•
L3-04 = 2 [Decel Stall Prevention Selection = Automatic Decel Reduction]
.
■
L3-20: DC Bus Voltage Adjustment Gain
No.
(Hex.)
Name
Description
Default
(Range)
L3-20
(0465)
Expert
DC Bus Voltage Adjustment
Gain
Sets the proportional gain used to control the DC bus voltage.
Determined by A1-02
(0.00 - 5.00)
Set one of these parameters to enable L3-20:
•
L2-29 = 1 [KEB Method Selection = Single Drive KEB Ride-Thru 2]
•
L3-04 = 2 [Decel Stall Prevention Selection = Automatic Decel Reduction]
•
L3-11 = 1 [OV Suppression Function Select = Enabled]
•
H1-xx = 7A or 7B [MFDI Function Select = KEB Ride-Thru 2 (N.O./N.C.)]
Note:
•
If stall prevention during deceleration function causes
ov [Overvoltage]
and
Uv1 [DC Bus Undervoltage]
faults when you start deceleration
and
L2-29 = 1, H1-xx = 7A or 7B
, or
L3-04 = 2
, gradually increase this parameter in 0.1-unit increments. If the setting value is too high, it
can cause large speed or current ripples.
•
If sudden increases in the regenerative load cause
ov
faults and
L3-11
= 1, gradually increase this parameter in 0.1-unit increments. If the
setting value is too high, it can cause large speed or current ripples.
■
L3-21: OVSuppression Accel/Decel P Gain
No.
(Hex.)
Name
Description
Default
(Range)
L3-21
(0466)
Expert
OVSuppression Accel/Decel
P Gain
Sets the proportional gain to calculate acceleration and deceleration rates.
Determined by A1-02
(0.10 - 10.00)
Set one of these parameters to enable L3-21:
•
L2-29 = 1 [KEB Method Selection = Single Drive KEB Ride-Thru 2]
•
L3-04 = 2 [Decel Stall Prevention Selection = Automatic Decel Reduction]
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...