YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
895
■
H6-07: Terminal MP Frequency Scaling
No.
(Hex.)
Name
Description
Default
(Range)
H6-07
(0432)
RUN
Terminal MP Frequency
Scaling
Sets the frequency of the pulse train output signal used when the monitor set with
H6-06 [Terminal
MP Monitor Selection]
is 100%.
1440 Hz
(0 - 32000 Hz)
When
H6-06 = 102 [Terminal MP Monitor Selection = Output Frequency]
and
H6-07 = 0
, the pulse train output
terminal MP outputs the same frequency as the drive output frequency.
■
H6-08: Terminal RP Minimum Frequency
No.
(Hex.)
Name
Description
Default
(Range)
H6-08
(043F)
Terminal RP Minimum
Frequency
Sets the minimum frequency of the pulse train signal that terminal RP can detect.
0.5 Hz
(0.1 - 1000.0 Hz)
•
When you input a pulse train frequency that is less than the value of
H6-08
, the pulse train input is 0.0 Hz.
•
Set
H6-01 [Terminal RP Pulse Train Function]
=
0 [Frequency Reference]
,
1 [PID Feedback Value]
, or
2 [PID
Setpoint Value]
to enable this parameter.
•
When
H6-01 = 3 [Speed Feedback (V/F Control)]
, the drive applies the setting of
F1-14 [Encoder Open-Circuit
Detect Time]
to the minimum frequency.
■
H6-09: Voltage Phase Sync MP Selection
No.
(Hex.)
Name
Description
Default
(Range)
H6-09
(156E)
Voltage Phase Sync MP
Selection
Set whether to output the pulse synchronized with drive output voltage phase from the pulse train
monitor output terminal MP. This parameter is only enabled when
H6-06 = 102 [Terminal MP
Monitor Selection = Output Frequency]
and
H6-07 = 0 [Terminal MP Frequency Scaling = 0 Hz]
.
0
(0, 1)
0 : Disabled
1 : Enabled
◆
H7: Virtual MFIO Selection
The virtual I/O function performs the following.
•
Inputs the result of the output from the MFDO terminal to the MFDI terminal without external wiring.
•
Inputs the result of the output from the MFAO terminal to the MFAI terminal without external wiring.
WARNING!
Sudden Movement Hazard. Before you do a test run, make sure that the setting values for virtual input and output
function parameters are correct. Virtual input and output functions can have different default settings and operation than wired input
and output functions. Incorrect function settings can cause serious injury or death.
Figure 12.117 Virtual Analog I/O Functional Block Diagram
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...