266
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
■
Enabling and Disabling the Drive Output (“Safe Torque Off”)
Refer to
for an example of drive operation when the drive changes from
“
Safe Torque Off
”
status to usual
operation.
Figure 5.20 Safe Disable Operation
Switching from Usual Operation to “Safe Torque Off”
Turn OFF (open) safety input terminal H1 or H2 to enable the Safe Disable function. When the Safe Disable function
is enabled while the motor is operating, the drive output and motor torque turn off and the motor always coasts to
stop. The
b1-03 [Stopping Method Selection]
setting does not have an effect on the stopping method.
The
“
Safe Torque Off
”
status is only possible with the Safe Disable function. Clear the Run command to stop the
drive. Turning off drive output (a baseblock condition) ≠
“
Safe Torque Off
”
.
Note:
•
When it is necessary to ramp to stop the motor, do not turn off terminals H1 and H2 until the motor fully stops. This will prevent the motor
from coasting to stop during usual operation.
•
A maximum of 3 ms will elapse from when terminals H1 or H2 shut off until the drive switches to the
“
Safe Torque Off
”
status. Set the OFF
status for terminals H1 and H2 to hold for at least 2 ms. The drive may not be able to switch to the
“
Safe Torque Off
”
status if terminals H1
and H2 are only open for less than 2 ms.
Going from “Safe Torque Off” to Usual Operation
The safety input will only release when there is no Run command.
•
During Stop
When the Safe Disable function is triggered during stop, close the circuit between terminals H1-HC and H2-HC to
disable
“
Safe Torque Off
”
. Enter the Run command after the drive stops correctly.
•
During Run
When the Safe Disable function is triggered during run, close the circuit between terminals H1-HC and H2-HC to
disable
“
Safe Torque Off
”
after clearing the Run command. Enter the Stop command, then enter the Run command
when terminals H1 and H2 are ON or OFF.
■
Safe Disable Monitor Output Function and Keypad Display
Refer to
for information about the relation between the input channel status, Safety monitor output status,
and drive output status.
Table 5.22 Safe Disable Input and External Device Monitor (EDM) Terminal Status
Input Channel Status
Safety Monitor Output Status
Drive Output
Status
Keypad Display
LED Status
Ring
MEMOBUS Register
0020H
Input 1
(H1-HC)
Input 2
(H2-HC)
MFDO Terminal
(H2-xx = 21)
MFDO Terminal
(H2-xx = 121)
bit C
bit D
ON
(Close the circuit)
ON
(Close the circuit)
OFF
ON
Baseblock
(Drive ready)
Normally
displayed
Ready:
Illuminated
0
0
OFF
(Open)
ON
(Close the circuit)
OFF
ON
Safety status
(STo)
SToF
(Flashing)
ALM/ERR:
Flashing
1
0
ON
(Close the circuit)
OFF
(Open)
OFF
ON
Safety status
(STo)
SToF
(Flashing)
ALM/ERR:
Flashing
1
0
OFF
(Open)
OFF
(Open)
ON
OFF
Safety status
(STo)
STo
(Flashing)
Ready: Flashing
0
1
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...