b5-35: PID Input Limit Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-35
(01A0)
RUN
PID Input Limit Level
Sets the output upper limit for the PID control as a percentage of the Maximum Output Frequency.
1000.0%
(0.0 - 1000.0%)
A large input value for PID control makes a high output. The drive applies this limit to the negative and positive
domains.
■
b5-36: PID High Feedback Detection Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b5-36
(01A1)
PID High Feedback
Detection Lvl
Sets the level that triggers
Excessive PID Feedback [FbH]
as a percentage of the Maximum Output
Frequency.
100%
(0 - 100%)
When the feedback signal increases to more than the level set in
b5-36
for the time set in
b5-37 [PID High Feedback
Detection Time]
, the drive will detect
Excessive PID Feedback [FbH]
.
■
b5-37: PID High Feedback Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-37
(01A2)
PID High Feedback
Detection Time
Sets the length of time that the PID feedback signal must be more than the level set in
b5-36 [PID
Feedback High Detection Lvl]
to cause
Excessive PID Feedback [FbH]
.
1.0 s
(0.0 - 25.5 s)
■
b5-38: PID User Unit Display Scaling
No.
(Hex.)
Name
Description
Default
(Range)
b5-38
(01FE)
PID User Unit Display
Scaling
Sets the value that the drive sets or shows as the PID setpoint when at the maximum output
frequency.
Determined by b5-20
(1 - 60000)
The drive uses this parameter and
b5-39 [PID Setpoint Display Digits]
together.
When
b5-20 = 3 [PID Unit Selection = User Units]
, the drive applies user-set PID setpoint and display units to these
parameters and monitors:
•
b5-19 [PID Setpoint Value]
•
b5-58 [PID Setpoint2]
•
b5-59 [PID Setpoint3]
•
b5-60 [PID Setpoint4]
•
U5-01 [PID Feedback]
•
U5-04 [PID Setpoint]
•
U5-99 [PID Setpoint Command]
■
b5-39: PID User Unit Display Digits
No.
(Hex.)
Name
Description
Default
(Range)
b5-39
(01FF)
PID User Unit Display
Digits
Sets the number of digits to set and show the PID setpoint.
Determined by b5-20
(0 - 3)
The drive uses this parameter and
b5-38 [PID Setpoint User Display]
together.
When
b5-20 = 3 [PID Unit Selection = User Units]
, the drive applies user-set PID setpoint and display units to these
parameters and monitors:
•
b5-19 [PID Setpoint Value]
•
b5-58 [PID Setpoint2]
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...