6.3 MEMOBUS/Modbus Communications
286
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Register No.
(Hex.)
Description
15DF
bit 0
Speed Search from Fmax
1: Enables Speed Search from Fmax
•
This is the same function as H1-xx = 61 [MFDI Function Selection = Speed Search from Fmax]. It operates as specified by the
command and OR operation from the MFDI terminals.
bit 1
Baseblock command
1: Enables baseblock command
•
This is the same function as H1-xx = 8 [Baseblock Command (N.O.)]. It operates as specified by the command and OR
operation from the MFDI terminals.
bit 2
Baseblock command - Without message
1: Enables baseblock command
•
This is the same function as H1-xx = 8 [Baseblock Command (N.O.)].
•
The keypad does not show the bb [Baseblock] alarm message. The ALM LED does not flash.
bit 3
Coast-to-stop command
1: Enables coast-to-stop command
•
The drive shuts off the output and the motor coasts to stop at the leading edge of bit 3.
•
To restart the drive, set bit 3 to 0 and enter the Run command again.
bit 4
Ramp to stop command
1: Enables ramp to stop command
•
The drive ramps to stop in the selected deceleration time at the leading edge of bit 4.
•
To restart the drive, set bit 4 to 0 and enter the Run command again.
bit 5
Fast stop command
1: Enables fast stop command
•
This is the same function as H1-xx = 15 [Fast Stop (N.O.)]. It operates as specified by the command and OR operation from the
MFDI terminals.
bit 6
Soft start input reset
1: Enables soft start input reset
•
When bit 6 is 1, the input to the soft starter will be 0. The drive decelerates the motor in the selected deceleration time. When
bit 6 is 0, the motor accelerates to the previous frequency reference.
•
U1-01 [Frequency Reference] shows the set frequency reference.
bit 7
Soft start output reset
1: Enables soft start output reset
•
When bit 7 is 1, the output from the soft starter will be 0.
•
When A1-02 = 3, 7 [Control Method Selection = Closed Loop Vector or PM Closed Loop Vector], the drive decelerates the
motor as specified by the torque limit. When A1-02 ≠ 3, 7, the drive shuts off the output and the motor coasts.
•
When bit 6 is 0, the motor accelerates to the previous frequency reference.
bit 8
Accel/decel ramp hold command
1: Enables accel/decel ramp hold command
•
This is the same function as H1-xx = A [Accel/Decel Ramp Hold]. It operates as specified by the command and OR operation
from the MFDI terminals.
bit 9
JOG command
1: Enables JOG command
•
This is the same function as H1-xx = 6 [Jog Reference Selection]. It operates as specified by the command and OR operation
from the MFDI terminals.
bit A
Forward Jog
1: Enables FJOG command
•
This is the same function as H1-xx = 12 [Forward Jog]. It operates as specified by the command and OR operation from the
MFDI terminals.
bit B
Reverse Jog
1: Enables RJOG command
•
This is the same function as H1-xx = 13 [Reverse Jog]. It operates as specified by the command and OR operation from the
MFDI terminals.
bit C
PID Disable command
1: Enables PID Disable command
•
This the same function as H1-xx = 19 [PID Disable]. It operates as specified by the command and OR operation from the
MFDI terminals.
bit D - F
Reserved
3004
Time Setting
Setting range: 0000 to 2359 (decimal), the default value at energize: 0000
Set the hour and the minute in HHMM format.
•
HH: 00 to 23 (decimal)
•
MM: 00 to 59 (decimal)
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...