736
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Figure 12.58 Setting a Variable Carrier Frequency to Agree with the Output Frequency
Note:
•
When
C6-05 ≤ 7
, the drive disables
C6-04
. The carrier frequency is fixed to the value set to
C6-03
.
•
The drive detects
oPE11 [Carrier Frequency Setting Error]
when these conditions are correct at the same time:
–
C6-05 ≥ 6
–
C6-04 ≥ C6-03
■
C6-04: Carrier Frequency Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
C6-04
(0226)
Carrier Frequency Lower
Limit
Sets the lower limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
Set
C6-03 [Carrier Frequency Upper Limit]
,
C6-04
, and
C6-05 [Carrier Freq Proportional Gain]
to make the carrier
frequency change linearly with the output frequency.
Note:
The drive detects
oPE11 [Carrier Frequency Setting Error]
when these conditions are correct at the same time:
•
C6-04 ≥ C6-03
•
C6-05 ≥ 6
■
C6-05: Carrier Freq Proportional Gain
No.
(Hex.)
Name
Description
Default
(Range)
C6-05
(0227)
Carrier Freq Proportional
Gain
Sets the proportional gain for the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection =
User Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(0 - 99)
Set
C6-03 [Carrier Frequency Upper Limit]
,
C6-04 [Carrier Frequency Lower Limit]
, and
C6-05
to make the carrier
frequency change linearly with the output frequency.
■
C6-09: Carrier Freq at Rotational Tune
No.
(Hex.)
Name
Description
Default
(Range)
C6-09
(022B)
Carrier Freq at Rotational
Tune
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to change this setting.
0
(0, 1)
If you set
C6-09 = 0
for a high-frequency or low-impedance motor, it can cause
oC [Overcurrent]
. To prevent
oC
, set
the carrier frequency to a high value and set
C6-09 = 1
before you do Auto-Tuning.
The procedure to set the carrier frequency when the
A1-02 [Control Method Selection]
setting changes.
•
When
A1-02 = 2, 3 [OLV, CLV]
, set
C6-02 = F [Carrier Frequency Selection = User Defined (C6-03 to C6-05)]
and then increase the value set to
C6-03 [Carrier Frequency Upper Limit]
.
•
When
A1-02 = 4 to 7 [AOLV, OLV/PM, AOLV/PM, or CLV/PM]
, use
C6-02
to increase the carrier frequency.
0 : 5kHz
Note:
When
A1-02 = 5, 6, 7 [Control Method Selection = OLV/PM, AOLV/PM, CLV/PM]
, the carrier frequency is 2 kHz.
1 : use C6-03
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...