n3-13: OverexcitationBraking (OEB) Gain
No.
(Hex.)
Name
Description
Default
(Range)
n3-13
(0531)
OverexcitationBraking
(OEB) Gain
Sets the gain value that the drive multiplies by the V/f pattern output value during overexcitation
deceleration to calculate the overexcitation level.
1.10
(1.00 - 1.40)
The V/f pattern output value goes back to its usual level after the motor stops or accelerates again to the frequency
reference speed.
The best value of this parameter changes when the flux saturation characteristics of the motor change.
•
Gradually increase the value of
n3-13
to 1.25 or 1.30 to increase the braking power of Overexcitation Deceleration.
If the gain is too much, the motor can have flux saturation and cause a large quantity of current to flow. This can
increase the deceleration time.
•
Decrease the setting value if flux saturation causes overcurrent. If you increase the setting value, the drive can
detect
oC [Overcurrent]
,
oL1 [Motor Overload]
, and
oL2 [Drive Overload]
. Decrease the value of
n3-21 [HSB
Current Suppression Level]
to prevent
oC
and
oL
.
•
Regular use of overexcitation deceleration or extended periods of overexcitation deceleration can increase internal
motor temperatures. Decrease the setting value in these conditions.
•
If
ov [Overvoltage]
occurs, increase the deceleration time.
■
n3-14: OEB High Frequency Injection
No.
(Hex.)
Name
Description
Default
(Range)
n3-14
(0532)
Expert
OEB High Frequency
Injection
Sets the function that injects harmonic signals during overexcitation deceleration.
0
(0, 1)
Enable this parameter to set a shorter deceleration time.
Note:
•
If you frequently use overexcitation deceleration on a motor, the motor loss will increase the risk of burn damage.
•
When you set this parameter to
1
, the motor can make a loud excitation sound during overexcitation deceleration. If the excitation sound is
unwanted, set this parameter to
0
to disable the function.
0 : Disabled
1 : Enabled
The drive injects harmonic signals at the time of overexcitation deceleration. You can decrease the deceleration time
because motor loss increases.
■
n3-21: HSB Current Suppression Level
No.
(Hex.)
Name
Description
Default
(Range)
n3-21
(0579)
HSB Current Suppression
Level
Sets the upper limit of the current that is suppressed at the time of overexcitation deceleration as a
percentage of the drive rated current.
100%
(0 - 150%)
If flux saturation during Overexcitation Deceleration makes the motor current become more than the value set in this
parameter, the drive will automatically decrease the overexcitation gain. If
oC [Overcurrent]
,
oL1 [Motor Overload]
,
or
oL2 [Drive Overloaded]
occur during overexcitation deceleration, decrease the setting value.
If repetitive or long overexcitation deceleration cause the motor to overheat, decrease the setting value.
■
n3-23: Overexcitation Braking Operation
No.
(Hex.)
Name
Description
Default
(Range)
n3-23
(057B)
Overexcitation Braking
Operation
Sets the direction of motor rotation where the drive will enable overexcitation.
0
(0 - 2)
0 : Disabled
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...