The Search Operation changes the output voltage in small increments to find a setpoint at which the drive can use
minimum power to operate.
Set this parameter to 0 to disable Search Operation. This will not disable Energy-saving control.
If the setting value is too low, the motor will stall when loads suddenly increase.
■
b8-16: PM E-Save Coefficient Ki
No.
(Hex.)
Name
Description
Default
(Range)
b8-16
(01F8)
Expert
PM E-Save Coefficient Ki
Sets torque linearity. This parameter uses the Ki value from the motor nameplate. Usually it is not
necessary to change this setting.
1.00
(0.00 - 3.00)
When
b8-16 = 1.00
(default), the drive will automatically calculate and control the energy-saving coefficient. If the
motor nameplate has a description for
“
Ki
”
, set this parameter to the Ki value.
Do this procedure to prevent oscillation when you set
b8-01 = 1 [Energy Saving Control Selection = Enabled]
.
1. Check
U5-21 [Energy Save Coeff Ki]
and make sure that it aligns with the Ki value on the motor nameplate.
2. If the numbers are different, set
b8-16
to the Ki value on the motor nameplate.
■
b8-17: PM E-Save Coefficient Kt
No.
(Hex.)
Name
Description
Default
(Range)
b8-17
(01F9)
Expert
PM E-Save Coefficient Kt
Sets torque linearity. This parameter uses the Kt value from the motor nameplate. Usually it is not
necessary to change this setting.
1.00
(0.00 - 3.00)
When
E5-01 = 1xxx, 2xxx [PM Motor Code Selection = Yaskawa SSR1 or SST4 series IPM motor]
, the drive
automatically calculates the energy-saving coefficient Kt and uses that value to control operation.
Do this procedure to prevent oscillation when you set
b8-01 = 1 [Energy Saving Control Selection = Enabled]
.
1. Check
U5-22 [Energy Save Coeff Kt]
and make sure that it aligns with the Kt value on the motor nameplate.
2. If the numbers are different, set
b8-17
to the Kt value on the motor nameplate.
■
b8-18: E-Save d-axis Current FilterTime
No.
(Hex.)
Name
Description
Default
(Range)
b8-18
(01FA)
Expert
E-Save d-axis Current
FilterTime
Sets the d-axis current reference filter time constant.
0.100 s
(0.000 - 5.000 s)
■
b8-19: E-Save Search Frequency
No.
(Hex.)
Name
Description
Default
(Range)
b8-19
(0B40)
Expert
E-Save Search Frequency
Sets the frequency of Energy-saving control search operations. Usually it is not necessary to change
this setting.
Determined by A1-02
(10 - 300 Hz)
Note:
•
If low inertia causes vibration in the machine, increase the setting value in 10 Hz increments and check the response. If
A1-02 = 8 [Control
Method Selection = EZOLV]
, increase the setting value in 1 Hz increments.
•
To make the motor more efficient, decrease the setting value in 1 Hz increments until the point immediately before machine vibration starts
to occur.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...