12.2 A: Initialization Parameters
650
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Figure 12.4 Holding Brake Open and Close Sequence Time Chart (CLV, CLV/PM)
*1
Start braking from the higher set frequency between
b2-01 [DC Injection/Zero SpeedThreshold]
or
E1-09 [Minimum Output Frequency]
.
Notes on when Using Other Functions
Function
Notes
Decel stall prevention function
When you connect a braking resistor to discharge the regenerative power to the drive, set
L3-04 = 0 [Stall Prevention during Decel =
Disabled]
.
Note:
If
L3-04 = 1 [General Purpose]
, it is possible that the drive will not stop in the set deceleration time. Do not change the default
settings of these related parameters:
•
L3-01 = 1 [Stall Prevention during Accel = Enabled]
•
L3-05 = 1 [Stall Prevention during RUN = Deceleration Time 1 (C1-02)]
Auto-Tuning for Induction Motors
•
When
A1-02 = 2, 3, 4 [Control Method Selection = Open Loop Vector, Closed Loop Vector, Advanced Open Loop Vector]
, Auto-Tune
the motor before you operate the drive.
•
Disconnect the drive from the motor to do Rotational Auto-Tuning.
•
Auto-Tuning runs automatically for approximately 1 minute. Do not do Auto-Tuning with the motor engaged in the elevator system.
Note:
•
If you cannot disconnect the motor from the machine, do Stationary Auto-Tuning. During this time, the drive automatically
measures the necessary motor data. If the motor test report or the motor nameplate is not available, use Stationary Auto-Tuning.
Do Stationary Auto-Tuning for Line-to-Line Resistance for better torque characteristics at low speeds in the V/f Control mode.
•
When you do Stationary Auto-Tuning, the drive energizes the motor and the motor stays stopped.
•
To Auto-Tune a specialized motor, for example a wound motor, prepare a motor test report before Auto-Tuning and make sure that
the motor parameter
E2-xx
is not too different than the value in the test report.
Auto-Tuning for PM Motors
You must set the motor data in the drive to run a PM motor.
•
When you use a PM motor recommended by Yaskawa
Input the motor code in
E5-01
.
E5
and other related motor parameters will be automatically set to the optimal values.
•
When you use a non-Yaskawa PM motor
Do Auto-Tuning.
–
When the motor nameplate or motor test report is available, enter the PM motor parameters directly with PM Motor Parameter
Settings.
–
If the motor nameplate or motor test report is not available, and the motor cannot rotate, do PM Stationary Auto-Tuning.
–
If the motor nameplate or motor test report is not available, and the motor can rotate, do PM Rotational Auto-Tuning.
–
When you replace an encoder, make sure that the motor can rotate and do Z Pulse Offset Tuning or PM Rotational Auto-Tuning.
Note:
•
Use in Closed Loop Vector Control for PM mode.
•
When you do Auto-Tuning or replace the encoder, make sure that the motor can rotate.
•
Set the Encoder Z-Pulse Offset.
•
Refer to Closed Loop Vector Control for induction motors for information about the signal to use and the adjustment method.
Braking Resistor Overheat Protection
When you use a braking resistor other than the optional Yaskawa braking resistor unit (LKEB-series), this function uses the thermal
overload relay to detect braking resistor overheat. Load a sequence program that turns OFF the drive input power supply when the
braking resistor overheats.
Note:
Refer to
when you load the sequence circuit.
Continuous operation function
Do not use the momentary power loss continuous operation function and the Auto Restart function. If you use these functions, there is a
risk that the motor will coast to a stop if the brake is open when there is a momentary power loss and the drive is operating or if there is a
fault.
Set the these parameters:
•
L2-01 = 0 [Power Loss Ride Through Select = Disabled]
•
L5-01 = 0 [Number of Auto-Restart Attempts = 0]
Torque limit function
The motor rated torque sets the value for
L7-01 to L7-04 [Torque Limit]
. If there will not be sufficient torque during start up, replace the
drive with a larger capacity drive and set the torque limit between 200% and 300%. The
L7-01 to L7-04
default setting is 200%.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...