Excessive PID Feedback [FbH]
Set these parameters to set how the drive detects a feedback level that is too high.
The drive detects too much PID feedback when the feedback value is more than the value in
b5-36
for longer than
the time in
b5-37
.
–
b5-12 [Feedback Loss Detection Select]
–
b5-36 [PID High Feedback Detection Lvl]
–
b5-37 [PID High Feedback Detection Time]
shows the operation principle when the feedback value is too low, and the drive detects feedback loss.
The operation is the same when the drive detects too much feedback.
Figure 12.36 Time Chart for PID Feedback Loss Detection Time
■
PID Sleep
PID sleep stops drive operation when the PID output or the frequency reference is less than
b5-15 [PID Sleep
Function Start Level]
. This function shuts off drive output after the motor decelerates to the set frequency.
The drive will automatically restart the motor when the PID output or the frequency reference is more than the
b5-15
value for the time set in
b5-16 [PID Sleep Delay Time]
.
shows the PID Sleep function.
Figure 12.37 PID Sleep Time Chart
Note:
•
The PID Sleep function is enabled when PID control is disabled.
•
When the PID Sleep function is triggered, the drive will stop the motor as specified by
b1-03 [Stopping Method Selection]
.
■
Fine-Tuning PID
Fine-tune the following parameter settings to have PID control eliminate problems with overshoot and oscillation.
•
b5-02 [Proportional Gain (P)]
•
b5-03 [Integral Time (I)]
•
b5-05 [Derivative Time (D)]
•
b5-08 [PID Primary Delay Time Constant]
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...