The drive reads the terminal status two times. The drive reads all changes to the terminal status two times to make
sure that the reading is the same.
The drive responds slower than when it reads the sequence one time, but this setting prevents malfunction because of
noise.
■
b1-07: LOCAL/REMOTE Run Selection
No.
(Hex.)
Name
Description
Default
(Range)
b1-07
(0186)
LOCAL/REMOTE Run
Selection
Sets drive response to an existing Run command when the drive receives a second Run command
from a different location.
0
(0, 1)
This parameter interlocks the drive to help prevent accidents that can occur if the motor starts to rotate because the
Run command source changed.
To switch the RUN command source, push
on the keypad or set
H1-xx = 1, 2 [MFDI Function Selection =
LOCAL/REMOTE Selection, External Reference 1/2 Selection]
and activate/deactivate the terminal.
0 : Disregard Existing RUN Command
If a Run command is enabled when you switch between Run command sources, the drive will not operate the motor.
When the drive is operating the motor, turn OFF the Run command to stop the motor. Enter the Run command again
to start operation.
1 : Accept Existing RUN Command
If a Run command is enabled when you switch between Run command sources, the drive will start to operate the
motor or continue to operate the motor.
WARNING!
Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default). If you do
not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate when you
energize the drive.
■
b1-08: Run Command Select in PRG Mode
No.
(Hex.)
Name
Description
Default
(Range)
b1-08
(0187)
Run Command Select in
PRG Mode
Sets the conditions for the drive to accept a Run command entered from an external source when
using the keypad to set parameters.
0
(0 - 2)
As a safety precaution, when the drive is in Programming Mode, it will not respond to a Run command.
This parameter helps prevent accidents that can occur if the motor starts to rotate because the drive received a Run
command from an external source while the user is programming the drive. You can also set the drive to not show the
Programming Mode when a Run command is active.
Note:
Refer to this table for Drive Mode and Programming Mode functions.
Mode
Keypad Screen
Function
Drive Mode
Monitors
Sets monitor display.
Programming Mode
Parameters
Changes parameter settings.
User Custom Parameters
Shows the User Parameters.
Parameter Backup/Restore
Saves parameters to the keypad as backup.
Modified Parameters/Fault Log
Shows modified parameters and fault history.
Auto-Tuning
Auto-Tunes the drive.
Initial Setup
Changes initial settings.
Diagnostic Tools
Sets data logs and backlight.
0 : Disregard RUN while Programming
The drive rejects the Run command while in Programming Mode.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...