YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
333
Code
Name
Causes
Possible Solutions
Electrical interference caused a drive malfunction.
•
Examine the control circuit lines, main circuit lines, and ground
wiring, and decrease the effects of electrical interference.
•
Make sure that a magnetic contactor is not the source of the
electrical interference, then use a Surge Protective Device if
necessary.
The load inertia is set incorrectly.
•
Examine the load inertia settings with KEB, overvoltage
suppression, or stall prevention during deceleration.
•
Adjust
L3-25 [Load Inertia Ratio]
to match the qualities of the
machine.
The Short Circuit Braking function used in OLV/PM
control method.
Connect a braking resistor to the drive.
There is motor hunting.
•
Adjust
n1-02 [Hunting Prevention Gain Setting]
.
•
Adjust
n2-02 [Automatic Freq Regulator Time 1]
and
n2-03
[Automatic Freq Regulator Time 2]
.
•
Adjust
n8-45 [Speed Feedback Detection Gain]
and
n8-47 [Pull-
in Current Comp Filter Time]
.
Speed Search at Start does not complete correctly
when:
•
A1-02 = 8 [Control Method Selection = EZOLV]
•
E9-01 = 0 [Motor Type Selection = Induction
(IM)]
Set
b3-24 = 2 [Speed Search Method Selection = Current Detection
2]
.
Note:
•
The drive detects this error if the DC bus voltage is more than the
ov
detection level while the drive is running.
•
Do a Fault Reset to clear the fault.
•
For 200 V class drives, the detection level of
ov
is approximately 410 V. For 400 V class drives, the detection level is approximately 820 V.
•
L5-08 [Fault Reset Enable Select Grp2]
disables the Auto Restart function.
Code
Name
Causes
Possible Solutions
PE1, PE2
PLC Faults
The communication option detected a fault.
Refer to the manual for the communication option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
PF
Input Phase Loss
There is a phase loss in the drive input power.
Correct errors with the wiring for main circuit drive input power.
There is loose wiring in the drive input power
terminals.
Tighten the terminal screws to the correct tightening torque.
The drive input power voltage is changing too much.
•
Examine the input power for problems.
•
Make the drive input power stable.
•
If the input power supply is good, examine the magnetic
contactor on the main circuit side for problems.
There is unsatisfactory balance between voltage
phases.
•
Examine the input power for problems.
•
Make the drive input power stable.
•
Set
L8-05 = 0 [Input Phase Loss Protection Sel = Disabled]
.
The main circuit capacitors have become
unserviceable.
•
Examine the capacitor maintenance time in monitor
U4-05
[CapacitorMaintenance]
. If
U4-05
is more than 90%, replace the
control board or the drive. For information about replacing the
control board, contact Yaskawa or your nearest sales
representative.
•
If drive input power is correct and the fault stays, replace the
control board or the drive. For information about replacing the
control board, contact Yaskawa or your nearest sales
representative.
Note:
•
The drive detects this error if the DC bus voltage changes irregularly without regeneration.
•
Do a Fault Reset to clear the fault.
•
Use
L8-05
to enable and disable
PF
detection.
Code
Name
Causes
Possible Solutions
PGo
Encoder (PG) Feedback Loss
The encoder cable is disconnected or wired
incorrectly.
Examine for wiring errors or disconnected wires in the encoder
cable, and repair problems.
The encoder is not receiving power.
Examine the encoder power supply.
The holding brake is stopping the motor.
Release the holding brake.
Note:
•
The drive detects this error if it does not receive the speed detection pulse signal from the encoder in the detection time set in
F1-14 [Encoder Open-Circuit Detect Time]
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this error, it will operate the motor as specified by the Stopping Method set in
F1-02 [PG Open Circuit Detection Select]
.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...