YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
701
0 : Standard
1 : EZ Sleep/Wake-up
■
b5-90: EZ Sleep Unit
No.
(Hex.)
Name
Description
Default
(Range)
b5-90
(0B90)
EZ Sleep Unit
Sets the measurement units for
b5-91 [EZ Sleep Minimum Speed]
and
b5-92 [EZ Sleep Level]
.
0
(0, 1)
0 : 0.1Hz units
1 : rev/min
■
b5-91: EZ Sleep Minimum Speed
No.
(Hex.)
Name
Description
Default
(Range)
b5-91
(0B91)
RUN
EZ Sleep Minimum Speed
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the largest value
from
b5-91
,
b5-34 [PID Output Lower Limit Level]
, and
d2-02 [Frequency Reference Lower Limit]
.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
Note:
The value of
b5-90 [EZ Sleep Unit]
sets the units. When
b5-90
changes, this parameter does not automatically update. Set this parameter
again after you change
b5-90
is changed.
■
b5-92: EZ Sleep Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-92
(0B92)
RUN
EZ Sleep Level
Sets the value that the output frequency or motor speed must be less than for longer than
b5-93 [EZ
Sleep Time]
to enter Sleep Mode.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
Note:
When
b5-90 [EZ Sleep Unit]
changes, this parameter does not automatically update. Set this parameter again after you change
b5-90
.
■
b5-93: EZ Sleep Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-93
(0B93)
RUN
EZ Sleep Time
Sets the length of time that the output frequency or motor speed must be less than
b5-92 [EZ Sleep
Level]
to enter Sleep Mode.
5.0 s
(0.0 - 1000.0 s)
■
b5-94: EZ Sleep Wake-up Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-94
(0B94)
RUN
EZ Sleep Wake-up Level
Sets the level at which the drive resumes operation when exiting Sleep Mode.
0.00%
(0.00 - 600.00%)
Note:
The values of
b5-20 [PID Unit Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-39 [PID User Unit Display Digits]
set the units.
When
b5-20
,
b5-38
, and
b5-39
change, this parameter does not automatically update. Set this parameter again after you change
b5-20
,
b5-38
,
and
b5-39
are changed.
•
When
b5-95 = 0 [EZ Sleep Wake-up Mode = Absolute]
:
When
b5-09 = 0 [PID Output Level Selection = Normal Output (Direct Acting)]
, and the PID Feedback
[H3-xx =
B]
is less than the value of
b5-94
for a time longer than the value of
b5-96 [EZ Sleep Wake-up Time]
, the drive will
exit sleep and start operation again. When
b5-09 = 1 [Reverse Output (Reverse Acting)]
, and the PID feedback is
more than setting value of
b5-94
for a time longer than the setting value of
b5-96
, the drive will exit sleep and start
operation again.
•
When
b5-95 = 1 [Setpoint Delta]
:
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...