844
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
When you activate the terminal set for Up2 Command, the bias will increase. When you activate the terminal set for
Down 2 Command, the bias will decrease. When you activate or deactivate the two commands, the drive will hold the
frequency reference.
Note:
•
When using this function, set the optimal bias limit value with
d4-08 and d4-09 [Up/Down 2 Bias Upper Limit/Lower Limit]
.
•
Refer to
“
d4: Frequency Ref Up/Down & Hold
”
for more information.
■
77: ASR Gain (C5-03) Select
Setting Value
Function
Description
77
ASR Gain (C5-03) Select
Sets the function to switch the ASR proportional gain set in
C5-01 [ASR Proportional Gain 1]
and
C5-03 [ASR Proportional Gain
2]
.
ON : C5-03
Switches the proportional gain to
C5-03 [ASR Proportional Gain 2]
.
OFF : C5-01
Switches the proportional gain to
C5-01 [ASR Proportional Gain 1]
.
Note:
Refer to
“
C5: Automatic Speed Regulator (ASR)
”
for more information.
■
78: Analog TorqueRef Polarity Invert
Setting Value
Function
Description
78
Analog TorqueRef Polarity
Invert
Sets the rotation direction of the external torque reference.
ON : External torque reference reverse direction
OFF : External torque reference forward direction
■
7A: KEB Ride-Thru 2 Activate (N.C.)
Setting Value
Function
Description
7A
KEB Ride-Thru 2 Activate
(N.C.)
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The
L2-29
[KEB Method Selection]
setting will not have an effect.
Note:
•
If you set
KEB Ride-Thru 1 [H1-xx = 65, 66]
and
KEB Ride-Thru 2 [H1-xx = 7A, 7B]
at the same time, the drive will detect
oPE03 [Multi-
Function Input Setting Err]
.
•
Refer to
“
KEB Ride-Thru function
”
for more information.
■
7B: KEB Ride-Thru 2 Activate (N.O.)
Setting Value
Function
Description
7B
KEB Ride-Thru 2 Activate
(N.O.)
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The
L2-29
[KEB Method Selection]
setting will not have an effect.
Note:
•
If you set
KEB Ride-Thru 1 [H1-xx = 65, 66]
and
KEB Ride-Thru 2 [H1-xx = 7A, 7B]
at the same time, the drive will detect
oPE03 [Multi-
Function Input Setting Err]
.
•
Refer to
“
KEB Ride-Thru function
”
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...