SIEPC71061737B GA800 Drive Technical Reference
■
F: Not Used
Setting Value
Function
Description
F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
Through Mode uses the signal input to the terminal as a digital input for the upper sequence through a communication
option or MEMOBUS/Modbus communications. This input signal does not have an effect on drive operation.
■
10: Up Command
Setting Value
Function
Description
10
Up Command
Sets the command to use a push button switch to increase the drive frequency reference. You must also set
Setting 11 [Down
Command]
.
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
Note:
•
If you set only the Up command or only the Down command, the drive will detect
oPE03 [Multi-Function Input Setting Err]
.
•
If you set two or more of these functions at the same time, the drive will detect
oPE03
:
–
Up/Down command
–
Accel/Decel Ramp Hold
–
Reference Sample Hold
–
Offset Frequency 1, 2, 3 addition
–
Up/Down 2 Command
•
The Up/Down command does not function in these conditions:
–
b1-01 = 2, 3 [Frequency Reference Selection 1 = Memobus/Modbus Communications, Option PCB]
–
b1-02 ≠ 1 [Run Command Selection 1 ≠ Control Circuit Terminal]
–
Drive is in LOCAL mode
–
Set to
b1-15 [Frequency Reference Selection 2]
by use of
H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection]
When you enter the UP command, the frequency reference increases. When you enter the Down command, the
frequency reference decreases.
The Up and Down commands have priority over all other frequency references. When you enable the Up/Down
command, the drive will ignore these frequency references:
•
Frequency reference from Keypad
[b1-01 = 0]
•
Frequency reference from Analog Input
[b1-01 = 1]
•
Frequency reference from Pulse Train Input
[b1-01 = 4]
shows the Up and Down commands with their operation.
Table 12.56 Up Command and Down Command
Command status
Drive operation
Up command (10)
Down command (11)
OFF
OFF
Keeps the current frequency reference.
ON
OFF
Increases the frequency reference.
OFF
ON
Decreases the frequency reference.
ON
ON
Keeps the current frequency reference.
Combine Frequency Reference Hold Functions and Up/Down Commands
•
When you clear the Run command or when
d4-01 = 0 [Freq Reference Hold Selection = Disabled]
, and you restart
the drive, the Up/Down command resets to 0.
•
When
d4-01 = 1 [Enabled]
, the drive saves the frequency reference set during the Up/Down command. When you
cycle the Run command or restart the drive, the drive saves the frequency reference value and restarts the motor at
this frequency value. After you clear the Run command, activate the terminal set for the Up command or Down
command to set the saved reference value to 0.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...