SIEPC71061737B GA800 Drive Technical Reference
10.7
Drive Derating
You must derate the drive capacity to operate the drive above the rated temperature, altitude, and default carrier
frequency.
◆
Carrier Frequency Settings and Rated Current Values
, and
show how the drive rated output current changes when the
C6-02 [Carrier
Frequency Selection]
value changes. The output current value changes linearly as the carrier frequency changes. You
can use the values from the tables to calculate a frequency that is not shown. When
A1-02 = 4, 6 [Control Method
Selection = AOLV, AOLV/PM]
, refer to
, and
■
200 V Class
Table 10.17 Carrier Frequency and Rated Current Derating
Model
Rated Current (A)
Heavy Duty Rating (HD)
Parameter C6-01 = 0
Normal Duty Rating (ND)
Parameter C6-01 = 1
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2004
3.5
3.5
3.5
3.4
3.2
3.06
4.2
4.0
3.6
3.4
3.1
2.77
2006
5.0
5.0
5.0
4.8
4.6
4.3
6
5.6
5
4.6
4.1
3.6
2008
6.9
6.9
6.9
6.5
5.9
5.4
8
7.6
6.9
6.5
5.9
5.4
2010
8.0
8.0
8.0
7.4
6.6
5.8
9.6
9.0
8
7.4
6.6
5.8
2012
11.0
11.0
11.0
10.4
9.6
8.8
12
11.7
11
10.5
9.9
9.3
2018
14.0
14.0
14.0
12.6
10.8
9.1
17.5
16.1
14
12.6
10.8
9.1
2021
17.5
17.5
17.5
16.1
14.3
12.6
21
19.6
17
16.1
14.3
12.5
2030
25.0
25.0
25.0
23.0
20.5
18.0
30
28.0
25
23.0
20.5
18.0
2042
33.0
33.0
33.0
29.3
24.8
20.2
42
38.4
33
29.4
24.9
20.4
2056
47.0
47.0
47.0
43.4
38.9
34.4
56
52.4
47
43.4
38.9
34.4
2070
60.0
60.0
60.0
56.0
51.0
46
70
66.0
60
56.0
51.0
46.0
2082
75.0
75.0
75.0
68.6
60.5
53
82
82.0
75
68.8
61.0
53.1
2110
88.0
88.0
88.0
80.5
71.0
62
110
102.7
92
84.3
75.2
66.0
2138
115.0
115.0
115.0
105.1
92.8
81
138
128.8
115
105.8
94.3
82.8
2169
145.0
145.0
125.2
112.0
-
-
169
152.7
128.3
112.0
-
-
2211
180.0
180.0
155.2
138.6
-
-
211
190.2
158.9
138.1
-
-
2257
215.0
215.0
184.8
164.7
-
-
257
230.4
190.5
163.9
-
-
2313
283.0
283.0
249.0
226.4
-
-
313
288.5
251.7
227.1
-
-
2360
346.0
346.0
294.3
259.8
-
-
360
330.8
287.6
258.8
-
-
2415
415.0
415.0
365.2
332.0
-
-
-
-
-
-
-
-
Table 10.18 AOLV
,
AOLV/PM Carrier Frequency and Rated Current Derating
Model
Rated Current (A)
Heavy Duty Rating (HD)
Parameter C6-01 = 0
Normal Duty Rating (ND)
Parameter C6-01 = 1
2 kHz
(2 kHz)
4 kHz
(-)
6 kHz
(5 kHz)
8 kHz
(8 kHz)
10 kHz
(10 kHz)
12 kHz
(12.5 kHz)
2 kHz
(2 kHz)
4 kHz
(-)
6 kHz
(5 kHz)
8 kHz
(8 kHz)
10 kHz
(10 kHz)
12 kHz
(12.5 kHz)
2004
3.5
3.5
3.4
3.2
3.1
2.9
4.2
3.8
3.5
3.1
2.8
2.4
2006
5.0
5.0
4.9
4.6
4.3
4.1
6.0
5.4
4.8
4.2
3.6
3.0
2008
6.9
6.9
6.7
6.0
5.4
4.7
8.0
7.3
6.7
6.0
5.4
4.7
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...