5.3 Motor
Terminal/Ground
<TB2>
Crimp terminal: N5.5-4
(made by J.S.T.)
4kW class AWG#12
Red
White
Black
Green or green/yellow
Motor cable
Yokogawa's motor cables are twisted pair cables with a common shield with the motor ground
cable. The shield is connected to the ground by connecting the motor ground cable to the
ground terminal.
If you provide your own cable, make sure to connect the shield to the ground terminal.
The tightening torque of the terminal block screw is 1.8 N-m and the matching wire size is
AWG#10 to 12. If a wire whose size does not match this specification is connected to the
terminal block, be sure to use a crimp terminal of the UL or CSA standard that matches the
wire size. Use crimp tools specified by the manufacturer.
Cable Specifications
Cable
Specification
4kW class
Motor
AWG#12 (3.5mm
2
) or more, length 30m or less
Motor terminal processing code
"-08"
Optional cable type name
(CIM-NE
-0306-
)
Ground
AWG#14 (2.0mm
2
) or more (Use as thick a cable as possible.)
Class 3 ground (ground resistance 100
Ω
or less)
Tightening torque of the terminal screws:
1.2N-m (12kgf-cm) (terminal screws: M4
×
0.7)
Make sure to perform ground in order to avoid electric shock accidents. Moreover, make sure
to connect the GND terminals of the motor and the drive.
!
DANGER
CAUTION
CAUTION