2-18
TI71M01D06-01EN 3rd Edition: 2012.12.01
(1) 4 kW Class Drives
•
This drive class utilizes a built-in fan to obtain forced air cooling.
•
Install the drive vertically, with the front panel facing forward. Do not install it with the
panel surface facing upward or downward, up side down or sideways (see the figures
below).
•
Allow a clearance of 50mm or more above and below the drive and 25mm or more on the
left and right sides for ventilation. Moreover, do not block the airflow of the fan (see the
figures below).
•
The power consumption used by the drive itself is based upon the "drive current" and is
defined by the suffix code. The "E" (50 A) drive is 250 W.
Do not install sideways
Do not install up side down
25mm
25mm
50
m
m
50
m
m