6-14
TI71M01D06-01EN 3rd Edition: 2012.12.01
(5) How to Change Logic (Soft) I/O Initial Value Setting
Set the initial values for logic I/O inputs using the utility software.
At shipment from the factory, the initial values of all logic I/O inputs are set to off. To change
the initial values of logic I/O inputs, perform the following operation.
STEP 1
Select [I/O] in Data Management of the utility software to display the I/O setting
window.
STEP 2
Select [Logic I/O initial value] in Type.
STEP 3
Select the logic I/O block to be changed from [Block].
STEP 4
Check the check box under the Initial value setting field for each item to be
changed (check the box to turn the signal ON).
STEP 5
Click the [Regist] button to register the settings in the drive.
Drive software is rebooted automatically.
2 Select [Logic I/O
Initial Value].
3 Select a logic
I/O block.
5 Register the settings
in the drive.
4 Set the initial value.
Checked: On
Unchecked: Off
* All signals are set to OFF at
shipment from the factory.